Metso neles ND7000H Operating Instructions Manual page 66

Intelligent valve controller
Table of Contents

Advertisement

66
ND9100H - Dev v3, DD v3:
Main Menu:
1 Main Menu
1 Configuration
2 Input Signal
17.5 mA
2 Calibrations
3 mA-Setpoint
84.6 %
3 Valve Offline Tests
4 Target Setpoint
85.2 %
4 Diagnostics
5 Valve Travel
85.2 %
5 Positioner Information
6 Temperature
24.7 ºC
6 Units
7 Supply Pressure
4.9 bar
7 Device Lock
8 Pressure Difference
1.8 bar
8 Dynamic Variables
MENU
METHOD
Editable variable
Read-only variable
in ND9000HT only
Assembly Related:
Configuration:
1 Assembly Related
1 Valve Type
2 Signal Modification
2 Actuator Type
3 Flow Modification
3 Valve Rotation Dir.
4 Posit. Fail Action
5 Dead Angle (a0)
6 Performance Level
7 DAC Direction
Signal Modification:
1 Bypass Sign. Mod.
2 Signal Direction
3 Position Limit Low
4 Position Limit High
5 Travel Rate Open
6 Travel Rate Close
7 Low Cut-off
8 High Cut-off
9 Split Range Low
Split Range High
Select calibration:
Flow Modification:
1 Travel Calibration
1 Modification Type
2 Tuning
2 Shape Factor
3 Travel Calib. and Tuning
3 Predefined Curves
4. 1pt-Calibration
4 User Defined Curve
Valve Offline Tests:
Select which Offline Test to start:
1 Start Offline Tests
1 Multipoint Step Test
2 Test Key Figures
2 Dynamic Loop Test
3 Valve Analysis Test
4 Valve Deadband Test
Test Key Figures:
1 Multipoint Step Test Key Figures
2 Dynamic Loop Test Key Figures
3 Valve Analysis Test Key Figures
4 Valve Deadband Test Key Figures
Warning Limits:
Diagnostics:
1 Warning Limits
1 Total Oper. Time
2 Alarm Limits
2 Valve Total Travel
3 Counters
3 Valve Travel Trend
4 Events
4 Valve Reversals
5 Device Status
5 Valve Reversals Trend
6 Alarms Disabled
6 Valve Rev.SSP Trend
7 Device Status
7 Actuator Total Travel
8 Actuator Reversals
9 Spool Total Travel
Spool Reversals
Setpoint Reversals Trend
Steady State Dev.
Dynamic State Dev.
Stiction Low
Stiction High
Load for Open Low
Load for Open High
Alarm Limits:
1 Supply Press. Low Lim.
2 Supply Press. High Lim.
3 Supply Press. Latch Time
4 Temp. Low Limit
5 Temp. High Limit
6 Temp. Latch Time
7 Ssdev Alarm Limit
8 Ssdev. Latch Time
9 Stiction Low Limit
Stiction High Limit
Stiction Latch Nbr
LfO Low Alarm Limit
LfO High Alarm Limit
LfO Latch Number
Counters:
1 Total Oper. Time
2 Valve Travel
3 Valve Reversals
4 Actuator Travel
5 Actuator Reversals
6 Setpoint Travel
7 Setpoint Reversals
8 Spool Valve Travel
9 Spool Valve Reversals
Reset Counters
Events:
1 All events
2 Notify events
3 Warning events
4 Error events
5 Alarm events
6 Failsafe events
Device Status:
Device Status:
Status Group 0, 1, 14, 15, 16, 17,
18, 19, 20, 21, 22, 23
Positioner Information:
Revision Information:
1 Revision Information
1 Device Type
2 Serial Numbers
2 Dev id
3 HART Related
3 Final asmbly num
4 Device Mode
4 Universal rev
5 Identify Device
5 Fld dev rev
6 Software rev
Units:
7 Hardware rev
1 Press. Diff. Unit
bar
2 Supply Pressure Unit
bar
Serial numbers:
3 Temperature Unit
ºC
1 VC Board Snbr.
2 HART Board Snbr.
Device Lock:
3 Device Serial Nbr.
1 Device Lock Status
...
4 DAC Board HW Rev.
2 Lock/Unlock Device
...
5 DAC Board SW Rev.
Dynamic Variables:
HART related:
PV is
...
1 Tag
SV is
...
2 Long tag
TV is
...
3 Date
QV is
...
4 Descriptor
5 Message
6 Poll addr.
7 Num req preams
8 Num. resp preams
9 Cfg chng count
Device Mode:
Identify Device:
Rotary, Linear, NelesCvGlobe, Linear No Comp
Double Acting, Single Acting
Clockwise, Counterclockwise
Fail to Close, Fail to Open
0.0 % [0..99%]
A(1)-Aggressive, b(1)-fast, C(1)-Optimum, d(1)-Stable, E-Max.
stability, (1) = Capac. Booster
Normal Direction, Reverse Direction, DAC Not Installed
No, Yes
Open, Close
0.0% [0..100%]
100.0 % [0..100%]
0.0 %/s [0..1000%/s]
0.0 %/s [0..1000%/s]
2.0 % [0..100%]
100.0 % [0..100%]
0.0 % [0..100%]
100.0 % [0..100%]
Linear (not used), Shape Factor, Custom Table
<1.0 = quick opening, 1.0 = linear, >1.0 = equal percent
0.100% defined in 5% increments
1..10 steps; start position, stop position, init time, duration
start position, stop position, init time, ramp time
target position, steady time, init time, ramp time
start position, init time, step wait time
216000.0 h [>=0h]
250000 [>=0]
2500.0 [>=0]
1000000 [>=0]
10000 [>=0]
5000 [>=0]
250000 [>=0]
1000000 [>=0]
10000000 [>=0]
10000000 [>=0]
10000 [>=0]
3.0 % [0..100%]
20.0 % [0..100%]
0.0 bar [0..20bar]
4.0 bar [0..20bar]
0.0 bar [0..10bar]
4.0 bar [0..10bar]
1.4 bar [1..8bar]
8.0 bar [1..8bar]
30.0 sec. [>0sec]
-40.0 ºC [-40..85ºC]
85.0 ºC [-40..85ºC]
120.0 sec. [>0sec]
5.0 % [0..100%]
30.0 sec. [>0sec]
0.0 bar [0..20bar]
10.0 bar [0..20bar]
10 [>1]
0.0 bar [0..10bar]
0.0 bar [0..10bar]
10 [>1]
670.23 h
105.42
223
105.42
223
115.42
233
279.38
843
Lists active alerts
All alert statuses by group
Off / On
ND9100H
1375803
174
YYWWNNNNBB
YYWWNNNNBB
TTYYWWNNNN
H029839-1.20
UNKNOWN
ND9000
ND9000
10/27/2014
ND9000
ND9000
134
Auto / Manual
Squawk
7 ND90 71 en
Select one of the Predefined Curves
1 Linear
2 1/25
3 Quick 1/25
4 1/33
5 Quick 1/33
6 1/50
7 Quick 1/50
Multipoint Step Test Key Figures:
1 Start Position
50.0 %
2 End Position
60.0 %
3 Testing Time
12.0 sec.
4 Dead Time Td
2.0 sec.
5 Step Response Time T86
4.4 sec.
6 Overshoot
12.3 %
7 Travel Gain
-1.2
Dynamic Loop Test Key Figures:
1 Start Position
10.0 %
2 End Position
100.0 %
3 Total Testing Time
100.0 sec.
4 Max. Dyn. Error
0.1 %
5 Setpoint at Error
66.1 %
Valve Analysis Test Key Figures:
1 Target Position
50.0 %
2 Steady Time
12.0 sec.
3 Ramp Time
8.0 sec.
4 Static Hysteresis
1.2 %
5 Sensitivity
14.2 %
6 Load for Opening
0.6 bar
7 Seat Load
0.2 bar
8 SR O2C Close
0.0 bar
9 SR O2C Open
0.0 bar
SR C2O Close
0.0 bar
SR C2O Open
0.0 bar
Valve Deadband Test Key Figures:
1 Start Position
30.0 %
2 Testing Time
125.0 sec.
3 Deadband
3.6 %
Select which counter to reset:
1 Valve Travel Counters
2 Actuator Travel Counters
3 Setpoint Travel Counters
4 Spool Valve Travel Counters
5 All Trends and Speed Histograms
6 Valve Travel vs. Time Histogram
7 Event Log
0
6
3
1
Serial Number Format:
TT = positioner factory
YY = year (last 2 digits)
WW = week
NNNN = count
BB = board number
0
5
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Neles nd9000fNeles nd9000hNeles nd9000pNd7000hNd9000hNd9000f ... Show all

Table of Contents