7 ND90 71 en
7.
OPTIONS OF VALVE CONTROLLER
Internal 2-wire (passive) position transmitter. Analog position
feedback signal, output 4–20 mA, supply voltage 12–30 V DC,
external load resistance 0–780 Ω.
ND91_HXT, ND91_HZT, ND92_HXT, ND93_HXT, , ND93_HZT,
ND94_HXT:
II 1 G Ex ia IIC T6...T4 Ga
II 1 D Ex ta IIIC T90 °C Da
II 2 G Ex ib IIC T6...T4 Gb
II 2 D Ex tb IIIC T90 °C Db
Ui ≤ 28 V, Ii ≤ 120 mA, Pi ≤ 1 W, Ci ≤ 22 nF, Li ≤ 53 μH,
external load resistance 0–690 Ω.
ND91_HXT, ND91_HZT, ND92_HXT, ND93_HXT, ND93_HZ, T,
ND94_HXT:
II 3 G Ex nA IIC T6...T4 Gc
II 3 D Ex tc IIIC T90 °C Dc
Ui ≤ 30 V, Ii ≤ 152 mA
II 3 G Ex ic IIC T6...T4 Gc
II 3 D Ex tc IIIC T90 °C Dc
T
Ui ≤ 30 V, Ii ≤ 152 mA, Pmax = device limits itself, Ci ≤ 22 nF,
Li ≤ 53 μH, external load resistance 0–780 Ω.
ND91_HUT, ND92_HUT, ND94_HUT and ND93_HU1T:
Class I, Division 1, Groups A, B, C, and D; T4/T5/T6
Ex ia IIC T4/T5/T6 Ga
Class I, Zone 0 AEx ia IIC T4/T5/T6 Ga
Ui ≤ 28 V, Ii ≤ 120 mA, Pi ≤ 1 W, Ci ≤ 22 nF, Li ≤ 53 μH,
external load resistance 0–690 Ω.
Class I, Division 2, Groups A, B, C, and D; T4/T5/T6
Ex nA IIC T4/T5/T6 Gc or Ex nA ia IIC T4/T5/T6 Gc Ga
Class I, Zone 2 AEx nA IIC T4/T5/T6 Gc or Ex nA ia IIC T4/T5/T6 Gc Ga
Ui ≤ 30 V, Pmax = device limits itself, Ci ≤ 22 nF, Li ≤ 53 μH, external
load resistance 0–780 Ω
ND92_HE1T, ND92_HE2T, ND92_HE4T, ND92_HE5T,
ND92_HE7T, ND93_HE1T, ND93_HE5T, ND93_HE7T:
Ui ≤ 30 V, Pmax = device limits itself,
external load resistance 0–780 Ω.
Applicable to 5. sign "H".
Remote mounting
Applicable only to 3. sign "1"
Requires always external position measurement. For rotary
actuator see accessories type code.
Output values for:
R
HART
Uo(Voc) = 3.53V, Io(Isc) = 12.6mA, Po = 11.1 mW, Co(Ca) = 10nF,
Lo(La) = 10μH.
F
fieldbus and Profibus
OUNDATION
Uo(Voc) = 5.0V, Io(Isc) = 17.8mA, Po = 22.2mW, Co(Ca) = 10nF,
Lo(La) = 10μH.
Exhaust adapter. ND9100: 1x 1/2 NPT thread, ND9200 and
G
ND9300: 2 x 1/2 NPT thread.
Arctic temperature option.
Temperature range -53 – +85 °C / -64 – +185 °F
Applicable to 3. sign "2 and 3"
C
Applicable to 6. sign "X", "X7", "E1, "E2", "E7" and "U"
Not applicable to 7. sign J (External junction box)
Note, Limit switch may limit the temperature range
ND91_H, ND94_H, ND92_H and ND93_H:
External junction box for all 4–20 mA wirings, including position
transmitter, if applicable. Junction box is connected to the
enclosure, 2 pcs. M20 x 1.5 conduit entry.
ND91_F, ND92_ F, ND94_F, ND93_F, ND91_P, ND92_P, ND94_P
J
and ND93_P:
External junction box for wirings, including option for parallel
connection of external surge protector.
Junction box is connected to the enclosure,
2 pcs. M20 x 1.5 conduit entry.
Applicable to 6. sign "N", "N7", "X", "X7", "Z", "E1" , " E2" or "E7".
Y
Special construction.
8.
LIMIT SWITCH TYPE
Inductive proximity switches, 2 pcs.
IP66 / NEMA 4X enclosure. M20 x 1.5 conduit entry (2 pcs.).
Option E2: 1/2 NPT conduit entry (2 pcs.).
Limit switches applicable only with ND9100, ND9200 and
ND9300
Metso; SST Sensor Dual Module, NO, 8–125 V DC / 24–125 V AC
Temperature range -40° to +82 °C / -40° to +179 °F.
D33
Applicable to 6. sign "N", "N7", "E1", "E2", "E5" and "E7".
Usable up to SIL3 acc. to IEC61508.
Metso; Namur Sensor Dual Module, 6–29 V DC, > 3 mA; < 1 mA.
Temperature range -40° to +82 °C / -40° to +179 °F.
D44
Applicable to 6. sign "N", "N7", "U", "E1", "E2", "E5" and "E7".
Usable up to SIL3 acc. to IEC61508.
P+F; NJ2-12GK-SN, 2-wire type, DC; > 3 mA; < 1 mA, NAMUR NC.
Temperature range: -40° to +85 °C / -40° to +185 °F.
Not applicable to 6. sign "E4".
I02
Usable up to SIL3 acc. to to IEC61508
NOTE: In safety-related applications the sensor must be operated
with a qualified fail safe interface, such as P+F KFD2-SH-EX1.
P+F; NCB2-12GM35-N0, 2-wire type, DC; > 3 mA; < 1 mA,
NAMUR NC
I09
Temperature range: -25° to +85 °C / -13° to +185 °F.
Not applicable to 6. sign "E4"
Usable up to SIL2 acc. to IEC61508.
Omron E2E-X2Y1, 2-wire type; AC; <100 mA; 24–240 V AC.
I32
Temperature range: -40° to +85 °C / -40° to +185 °F.
Applicable to 6. sign "N", "N7", "E1", "E2", "E5" and "E7".
P+F, NJ4-12GK-SN, 2-wire, DC; > 3 mA; < 1 mA, NAMUR NC
Temperature range -50 ... +85 °C /-58 ... 185 °F)
I41
Applicable to 6. sign "N", "N7", "X", "X7", "U", "E1", "E2" or "E7".
Note that device may limit temperature range.
P+F; NJ3-18GK-S1N, 2-wire type, DC; > 3 mA; < 1 mA, NAMUR NO.
Temperature range: -25° to +85 °C / -13° to +185 °F.
I45
Not applicable to 6. sign "E4".
Usable up to SIL3 acc. to IEC61508.
ifm; IFC2002-ARKG/UP, 2-wire type, DC; 150 mA, 10–36 V DC,
leakage current < 0.6 mA.
I56
Temperature range: -20° to +85 °C / -4° to +185 °F.
Not applicable to 6. sign "X", "X7", "Z", "U" and "E4".
Mechanical micro switches, 2 pcs.
IP66 / NEMA 4X enclosure.
M20 x 1.5 conduit entry (2 pcs.).
Option E2: 1/2 NPT conduit entry (2 pcs.).
Limit switches applicable only with ND9100, ND9200 and
ND9300
Omron D2VW-5, 3 A - 250 V AC, 0.4 A - 125 V DC, 5 A - 30 V DC.
K05
Temperature range: -40° to +85 °C / -40° to +185 °F.
Not applicable to 6. sign "X", "X7", "Z", "U" and "E4".
Omron D2VW-01, gold plated contacts, 100 mA - 30 V DC /
125 V AC.
K06
Temperature range: -40° to +85 °C / -40° to +185 °F.
Not applicable to 6. sign "X", "X7", "Z", "U" and "E4".
Bus powered mechanical micro switches, 2 pcs.
Applicable to ND9000F and ND9000P only.
IP66 / NEMA 4X enclosure. M20 x 1.5 conduit entry (2 pcs.). Option
E2: 1/2 NPT conduit entry (2 pcs.).
Omron D2VW-01, gold plated contacts; Bus Powered,
no external power needed.
B06
Temperature range: -40° to +85 °C / -40° to +185 °F.
Not applicable to 5. sign "H".
Not applicable to 6. sign "E4".
9.