4.5.3 Remote mounting by using Metso ReC
If there is 4-20mA output from the position sensor, that
can't be connected directly to ND9100R. This kind of cases
there have to be ReC adapter which converts position sig-
nal suitable for ND9100 like shown in schematic picture
Connection terminals in Rec adapter:
Connection terminals in Rec adapter
NOTES:
1.
Cut the ND9 cable (RC01, RC02 or RC03) and the
Position sensor cable to optimal length for your
application. Then connect the individual wires as
shown in connection diagram.
2.
Connect positioner control (4...20mA) signal directly
to ND or alternatively to Pass through terminals IN+/
IN-, and Metso ND9 control input cable to OUT+/
OUT-.
4-20mA Pass Through connectors positive (+) ter-
minals are internally shorted, and negative (-) ter-
minals are internally shorted.
3.
Connector with "+24V" and "GND" shall be supplied
from external 24V (nominal 24 VDC, range is 18-30
VDC) voltage supply. This supply is powering the
converter and the external position sensor.
4.
Use proper cable cland or blind plug for each cable
entry.