Table 13 Ambient temperatures, ND9_N
Variant type
Ambien temperature ranges
ND_N_
-40° to +85 °C
ND_N_/I02
ND_N_/K05
ND_N_/K06
ND_N_/B06
ND_N_/I32
ND_N_/D33
-40° to +82 °C
ND_N_/D44
ND_N_/I45
-25° to +85 °C
ND_N_/I56
-25° to +80 °C
ND_NC_ (*
-53° to +85 °C
ND_NC_/I41 (*
-50° to +85 °C
Note *) Not allowed with external junction box (J, -40 °C)
Table 14 Ambient temperatures, ND9_U
Variant type
IS Class I, Division 1, Groups A, B, C, D, T4...T6
IS Class I, Zone 0, AEx ia, IIC T4...T6
Ambient temperature ranges
T6
ND9_U_
-40° to +50 °C
ND9_U/D44
Pending
ND9_U/I02
ND9_U/I09
ND9_U/I45
Table 15 Ambient temperatures, ND9_U
Variant type
NI Class I, Division 2, Groups A, B, C, D, T4...T6
NI Class I, Zone 2, Ex nA IIC T4...T6
Ambient temperature ranges
T6
ND9_U_
-40° to +50 °C
ND9_U/D44
Pending
ND9_U/I02
ND9_U/I09
ND9_U/I45
Table 16 Ambient temperatures, ND9_E2 (ND9_E4, only T6)
Variant type
Ex d IIC T4...T6, AEx d IIC T4...T6
Ex tb IIIC T100 °C IP66, AEx tb IIIC T100 °C IP66
Ambient temperature ranges
T6
ND9_E2
-40° to +60 °C
ND9_E2/I02
-40° to +60 °C
ND9_E2/I09
-25° to +60 °C
ND9_E2/I32
-25° to +60 °C
ND9_E2/D33
-40° to +60 °C
ND9_E2/D44
-40° to +60 °C
ND9_E2/I45
-25° to +60 °C
ND9_E2/K05
-40° to +60 °C
ND9_E2/IK06
-40° to +60 °C
ND9_E2/B06
-40° to +60 °C
Table 17 Ambient temperatures, ND9_Z Inmetro
Variant type
Ex ia IIC T4/T5/T6 Ga
Ex ia IIC T4/T5/T6 Gb
Ambient temperature ranges
T6
ND91_Z
-40° to +50 °C
ND91_Z/I02
-40° to +50 °C
ND91_Z/I09
-25° to +50 °C
ND91_Z/I45
-25° to +50 °C
Table 18 Ambient temperatures, ND9_Z Inmetro
Variant type
Ex nA IIC T4/T5/T6 Gc
Ex ic IIC T4/T5/T6 Gc
Ambient temperature ranges
T6
ND91_Z_
-40° to +60 °C
ND91_Z/I02
-40° to +60 °C
ND91_Z/I09
-25° to +60 °C
ND91_Z/I45
-25° to +60 °C
T5
T4
-40° to +65 °C
-40° to +80 °C
T5
T4
-40° to +65 °C
-40° to +80 °C
T5
T4
-40° to +75 °C
-40° to +85 °C
-40° to +75 °C
-40° to +85 °C
-25° to +75 °C
-25° to +85 °C
-25° to +70 °C
-25° to +70 °C
-40° to +75 °C
-40° to +82 °C
-40° to +75 °C
-40° to +82 °C
-25° to +75 °C
-25° to +85 °C
-40° to +75 °C
-40° to +85 °C
-40° to +75 °C
-40° to +85 °C
-40° to +75 °C
-40° to +85 °C
T5
T4
-40° to +65 °C
-40° to +80 °C
-40° to +64 °C
-40° to +80 °C
-25° to +65 °C
-25° to +80 °C
-25° to +64 °C
-25° to +80 °C
T5
T4
-40° to +75 °C
-40° to +85 °C
-40° to +75 °C
-40° to +85 °C
-25° to +75 °C
-25° to +85 °C
-25° to +75 °C
-25° to +85 °C
Table 19 Ambient temperatures, ND9_Z Inmetro
Variant type
Ex d IIC T4/T5/T6 Gb
Ex tb IIIC T100 °C Db IP66
Ambient temperature ranges
T6
ND9_E1_
-40° to +60 °C
ND9_E1/I02
ND9_E1/K05
ND9_E1/K06
ND9_E1/B06
ND9_E1/D33
-40° to +60 °C
ND9_E1/D44
ND9_E1/I09
-25° to +60 °C
ND9...E1/I45
ND9_E1/I56
-25° to +60 °C
ND9_E1/I32
-25° to +60 °C
9.2

Installation on a valve controller

The limit switch may be installed on an existing valve con-
troller.
ND9100
If the valve controller is already mounted on an actu-
ator/valve assembly, operate the actuator into the
closed or open position.
Remove the cover (100), the pointer (109), the LUI
(223), the prestage cover (43) and electronics cover
(39).
Turn the shaft (311) onto the shaft (11). Fasten the
screw (312) using a locking agent such as Loctite.
Unfasten the screws (314) in the cam discs (313).
Mount the electronics cover (39) and the housing
(300) on the valve controller.
ND9100/K00: Turn the cam discs (313) to avoid con-
tact with the micro switches, if required.
Mount the LUI (223) on the bed (306).
Mount the pointer (109) on the shaft (311). Adjust
the limit switch according to 9.4.
ND9200, ND9300
If the valve controller is already mounted on an actu-
ator/valve assembly, operate the actuator into the
closed or open position.
Remove the cover (100), the pointer (109), the LUI
(223) and electronics cover (39).
Turn the shaft (311) onto the shaft (11). Fasten the
screw (312) using a locking agent such as Loctite.
Mount the electronics cover (39) and the limit switch
housing (300) on the valve controller. Lock the hous-
ing in place with screw (326). Install the base plate
(324) with the limit switches and connector block
into the limit switch housing. Fasten the base plate
with screws (325), 3 pcs.
Install the cam discs (313) and bushings (346) to the
shaft.
Mount the LUI (223) on the holder (306).
Replace the plastic plugs with metal ones in conduit
entries which will not be used.
Mount the pointer (109) on the shaft (311). Adjust
the limit switch according to 9.4.
7 ND90 71 en
T5
T4
-40° to +75 °C
-40° to +85 °C
-40° to +75 °C
-40° to +82 °C
-25° to +75 °C
-25° to +85 °C
-25° to +75 °C
-25° to +80 °C
-25° to +70 °C
-25° to +70 °C