Configuration modes for digital inputs/outputs
3.3 Parameters/address space
3.3
Parameters/address space
3.3.1
Parameters
The following table shows the parameters for the DIQ 16x24VDC/0.5A 8xM12 digital input /
digital output module in the configuration modes for digital inputs and outputs.
Table 3- 12
Parameters
Diagnostics: Missing load voltage
2L+
Diagnostics: Short-circuit to ground
Reaction to CPU/master STOP
Freely configurable channel*
Substitute value channel
Input delay**
* = Can only be set in DIQ or DIQ with value status configuration mode.
** = Not available in DQ16 mode. Only values starting from 1.6 ms can be configured for the input
delay for channels 8..15.
22
Parameters
Digital input/Digital output module DIQ 16x24VDC/0.5A 8xM12 (6ES7143-5AH00-0BA0)
Value range
Default
Disable
Disable
•
Enable
•
Disable
Disable
•
Enable
•
Shut down
Shut down
•
Keep last value
•
Output substi-
•
tute value
DI
DI
•
DQ
•
0
0
•
1
•
3.2 ms
0.05 ms
•
0.1 ms
•
0.4 ms
•
0.8 ms
•
1.6 ms
•
3.2 ms
•
12.8 ms
•
20 ms
•
Scope
Module
Module
(Short-circuit of
encoder supply or
of the output to
ground)
Module
(digital outputs)
Channel
Channel
(digital outputs)
Channel
(Digital inputs)
Manual, 03/2019, A5E38688112-AC