Technical specifications
Article number
for technological functions
–
parameterizable
Cable length
unshielded, max.
•
Digital outputs
Number of digital outputs
in groups of
•
Short-circuit protection
Response threshold, typ.
•
Limitation of inductive shutdown voltage to
Digital output functions, parameterizable
Switching tripped by comparison values
•
Freely usable digital output
•
Switching capacity of the outputs
on lamp load, max.
•
Load resistance range
lower limit
•
upper limit
•
Output voltage
for signal "1", min.
•
Output current
for signal "1" rated value
•
for signal "0" residual current, max.
•
Switching frequency
with resistive load, max.
•
with inductive load, max.
•
on lamp load, max.
•
Total current of the outputs
Current per group, max.
•
Cable length
unshielded, max.
•
Encoder
Connectable encoders
2-wire sensor
•
–
permissible quiescent current (2-wire
sensor), max.
78
6ES7143-5AH00-0BA0
Yes
30 m
16; Parameterizable as DIQ
8; 2 load groups for 8 outputs each
Yes; per channel, electronic
0.7 A
L+ (-53 V)
Yes
Yes
5 W
48 Ω
4 kΩ
L+ (-0.8 V)
0.5 A
0.5 mA
100 Hz
0.5 Hz
1 Hz
4 A
30 m
Yes
1.5 mA
Digital input/Digital output module DIQ 16x24VDC/0.5A 8xM12 (6ES7143-5AH00-0BA0)