MAXA HI-T User's And Installer's Manual page 44

Lcd touch-screen centralized controller for hydronic terminal coupled with n-i-hwak/wp v2/v2+ minichillers and i-hp/i-hp lt chillers
Table of Contents

Advertisement

until n° 7 cascade chillers with terminal units not connected 
n°1 chiller with connected terminal units (until n° 80 terminal units) 
until n° 7 cascade chillers with terminal units connected (until n° 80 terminal units) 
 
The  chillers  connected  in  series  do  not  need  further  working  probes  to  be  placed  onto  the  system  total  discharge  piping  as  the 
centralized  system  acquires  the  single  temperature  of  every  unit  and  "thermal‐regulates"  as  per  the  average  discharge 
temperature. The advantage of a combined HNS system is mainly based on the fact that the user has the Hi‐T panel as the sole 
interface which, in an easy and intuitive way, allows the setting and the monitoring of the "hydronic units + chillers" system. It is 
possible  to  connect  in  cascade  also  chillers  having  different  capacities;  the  Hi‐T  control  will  be  capable  of  "self‐learning"  the 
installed capacity and of visualizing (by pressing F2 button and selecting the unit) in "real time", on the main menu, the percentage 
of provided capacity in comparison with the installed one (under installer's password). It is also possible, from the display of the 
main  controller,  to  know  the  working  hydronic  units  number  in  comparison  with  installed  ones  and  respecting  the  number  of 
running chillers connected in the network. 
 
 
SANITARY HOT WATER FUNCTION: the chillers can also provide sanitary water by managing an external 3‐way valve and 
a properly sized boiler. By connecting in cascade several chillers, the user can decide whether all or only just a few of them
used to supply "sanitary water". 
 
      CHRONOTHERMOSTAT  FUNCTION:  the  Hi‐T  remote  touch‐screen  control  contains  the  function  of  weekly 
chronothermostat  with  two  levels  of  temperature  T  and  Teco,  for  the  control  of  hydronic  terminals  and  chillers.  The  weekly 
programming is performed in separate way for hydronic terminals and for chiller (e.g., in a hypothetical office you can program the 
power‐on of the chiller 30 'before the opening time, so the water in the pipes  is heated/cooled and only 10' before the start of the 
activities the hydronic terminals are switched). Furthermore, the thermostat sets the weekly scheduling also for the production of 
domestic hot water and for the Legionella disinfection. 
 
 HUMIDITY CONTROL FUNCTIONS/DOUBLE SET POINT: humidity and temperature sensors integrated in the Hi‐T 
remote  control  enable  the  management  of  a  double  set‐point  adjustment  and  the  thermohygrometric  environmental  regulation. 
The remote control Hi‐T manages dehumidification for underfloor heating systems. 
43 
 
 
 
  Hi‐T
Centralized controller