4.10
CLIMATIC COMPENSATION
It is possible to compensate the set‐point according to outdoor temperature, in a different way between heating and cooling modes,
first and second set‐point.
In such a case be sure that the b08 parameter (System main page ‐> Configuration ‐> Service menu ‐> Parameters ‐> Chiller ‐> Chiller
name ‐> b08: Enab. dynamic set point) is disabled (=0) on the chiller.
Setpoint
Setpoint
Set
Set
•
Set = T water, T water ECO o T
•
Offset = offset settable from the page: "Set‐point setup" ‐> "Chiller" (the variable "Offset" appears only if the "m"
coefficients have been configured).
•
Set Text, m1, m2 = parameters which can be set from: "Configuration" ‐> "Service menu" ‐> "Parameters" ‐> "Keyboard"
(see parameters list in Table 4).
To exclude the climatic compensation by the user, you have to set to zero all the offsets in the menu "Set‐point setup" ‐> "Chiller".
To exclude the climatic compensation by the service, you have to set to zero the "m" coefficients in the service menu, keyboard
parameters.
The outdoor temperature is detected by a dedicated sensor already wired to the heat pump.
4.11
OTHER FUNCTIONS
For any information related to other functions of the chiller or of the fan coils which are shown in the Hi‐T display (e.g. enabling or
activation of plant electrical heater, sanitary electrical heater, boiler integration, defrosting cycle, water‐side or air‐side anti‐freeze
heaters, etc...), please refer to chiller or fan coil manuals.
4.12 SPECIAL FUNCTIONS
From the main menu, choosing the icon "additional functions", you go to the following menu:
35
m2
m2
m1
m1
Offset
Offset
Set Text
Set Text
Figure 29. Climatic compensation.
water, T
water ECO, settable from the page: "Set‐point setup" ‐> "Chiller".
2
2
Hi‐T
Offset
Offset
Centralized controller
T ext
T ext