In the configuration pages on the chronothermostat colourful time‐lines appear: the blue time‐line indicates normal operation, the 
green  time‐line  indicates  the  economical  operation,  the  red  time‐line  indicates  the  time  in  which  the  legionella  cycle  it  is 
programmed (thus the machine in that condition may be active even if the scheduler is set to Off). 
 
4.6.5.2
WEEKLY PROGRAMMING FAN COIL ZONE 
In  a  similar  way  to  the  scheduling  of  chillers,  a  weekly  program  of  each  zone  can  be  set  (independently  between  summer  and 
winter), with minimum steps of 15 minutes. 
The possible settings are: 
Off zone; 
Normal operation zone (normal ambient set‐point); 
Economical function zone (economic ambient set‐point). 
 
Going in "Summer Zone" or "Winter Zone" the list of all zones set is shown. At this point you need to choose the area you want to 
set; the configuration procedure on the chronothermostat is then equal to that one previously reported for the chiller. The features 
and the functionalities of the page are identical to those already described. 
 
4.6.5.3
WEEKLY PROGRAMMING SANITARY WATER PRODUCTION 
In a similar way to what is reported for the settings on the chronothermostat of chillers and fan coils, you can define when to enable 
the production of sanitary hot water (by setting the individual days of the week, with a minimum step of 15 minutes). The settings 
that you can do are: 
Normal: Enable function; 
Off: Disabled function. 
To set the programming, go to "Programs" ‐> "Sanitary" (the word "Sanitary" appears only if you have enabled the sanitary mode: 
System Main  ‐> Configuration ‐> Service menu ‐> Parameters ‐> Chiller ‐> Chiller name ‐> H10: Sanitary presence = 1). 
The  procedure  for  configuring  the  programmable  chronothermostat  is  therefore  similar  to  those  described  above,  with  the  only 
difference that the choice of the operation is only between "Normal" and "Off" (see figure below). 
 
 
In the period when the function is active, the machines enabled to produce sanitary water are placed in the seasonal operation of 
the plant scheduled by the plant scheduler with the addition of the sanitary mode, that is, respectively: 
Summer + sanitary 
Winter + sanitary  
Only sanitary  
 
4.6.5.4
LEGIONELLA DISINFECTION WEEKLY PROGRAM FUNCTION 
If the sanitary function is enabled (from system main page ‐> Configuration ‐> Service menu ‐> Parameters ‐> Chiller ‐> Chiller name ‐
>   H10:  Sanitary  presence  =  1),  you  can  program  the  hours  of  the  individual  days  of  the  week  for  activating  the  cycle  of  anti‐
legionella disinfection.  
You select only the starting time (with 15 minutes steps), since the duration of the cycle is defined by a parameter with maintainer 
access rights (System main page ‐‐> Configuration ‐> Service menu ‐> Parameters ‐> Keyboard ‐> Par 31/44:  Legionella disinfection 
enable time).
 To carry out the programming you must enter into "Programs" ‐> "Legionella disinfection"; the procedure is simple because you 
have to select only the starting day and hour for the cycle (see Figure below).
 
31 
 
 
Figure 26. Chronothermostat, "Sanitary" page. 
 