9. Icons of the navigation sidebar
3.4.1.1
ASSIGNMENT OF NAMES TO THE CHILLERS
For the assignment of the name to a chiller, you must navigate between the pages of the chiller connected to the network until you
get to the page of the chiller which you want to change the name: for apply this, you have to make single press into the pressure
sensitive area 4. Once you find the chiller, press and hold for a few seconds in the same area 4. Then compose with the keyboard
that appears the desired name.
The name of the chiller can have a maximum of 13 characters.
3.4.1.2
CHILLER AREA
The area 5 shown in Figure 10 gives indications about the operation (compressor running) of the chiller, graphically displaying the
fan rotation.
Pushing down on the area 5 you access to a further screen that shows a list of read data in real time related to the involved chiller:
•
Inlet water temperature (°C)
•
Outlet water temperature (°C)
•
Sanitary probe temperature (if it's present and configured, °C).
Accessing the same page with service or manufacturer access right (to enable the access right, press on the "configurations" icon
present in the sensitive area 8 of Figure 10 and set the service/manufacturer password), the data displayed in real‐time are:
•
Inlet water temperature (°C)
•
Outlet water temperature (°C)
•
Sanitary probe temperature (if it's present and configured)
•
High pressure (bar)
•
Low pressure (bar)
•
Compressor speed (Hz)
•
Opening expansion valve (step)
•
Fan speed (%)
•
Pump speed (%)
•
Overheating (°C)
•
Compressor operating hours (Hr.)
•
Pump operating hours (Hr.)
11
Figure 11. Insert chiller name.
Hi‐T
Centralized controller