Pin Assignment For The Positioner - Burkert 3280 Operating Instructions Manual

2-way motor valve
Hide thumbs Also See for 3280:
Table of Contents

Advertisement

Type 3280, 3285
Installation
7.2.3
pin assignment for the positioner
7.2.3.1
analog version, circular connector m12, 8-pole
3
4
2
8
5
6
1
7
* The indicated wire colors refer to the connection cable, order no. 919061, available as an accessory.
** 3.3 V signal voltage, reliable communication decreases as the line length and transfer rate increases.
7.2.3.2
Digital version, circular connector m12, 5-pole
4
1
5
3
2
* The indicated wire colors refer to the büS cables which are available as accessories.
pin
Wire colors*
configuration
1
white
Supply +
2
brown
Supply GND
3
green
CAN low
4
yellow
CAN high
5
grey
CAN GND
6
rose
Set-point value
input +
7
blue
Actual value
output
8
red
Signal GND
Body
Shielding
pin
Wire colors
configuration
*
1
Shielding
2
red
Supply +
3
black
GND
4
white
CAN high
5
blue
CAN low
external circuit
24 V DC ±10 %, max. residual ripple 10
%
24 V DC GND
CAN low
**
CAN high
**
CAN GND
**
0...20 mA / 4...20 mA / 0...5 V / 0...10 V,
not galvanically isolated
0...20 mA / 4...20 mA / 0...5 V / 0...10 V,
not galvanically isolated
Signal GND
-
external circuit
24 V DC ±10 %, max. residual ripple 10
%
GND
CAN high
CAN low
english