3
SPECIFICATIONS

3.4.6 A/D conversion completed flag (buffer memory address 10: Un\G10)

3 - 55
POINT
For the channel where the value outside the above setting range has been written,
operation is performed by sampling processing.
(1)
When A/D conversion for the channels enabled for conversion is complete, the
A/D conversion completed flag is set to 1.
The A/D conversion completed flag (XE) is set to ON when the conversion for all
A/D conversion enabled channels is complete.
(2)
When the operating condition setting request (Y9) is set to ON, the flag returns
to the default setting of 0 and changes to 1 when A/D conversion is complete.
b15 b14 b13 b12 b11 b10
0
0
0
For Q64AD-GH, information of b4 to b15 is fixed at 0.
For Q62AD-DGH, information of b2 to b15 is fixed at 0.
[Setting example of Q64AD-GH]
When all conversions of channels 1 and 2 enabled for A/D conversion are
completed, 0003
b15
b14 b13 b12 b11 b10
0
0
0
0
0
[Setting example of Q62AD-DGH]
When conversion of channel 2 enabled for A/D conversion is completed, 0002
(2) is stored into the buffer memory address 10 (Un\G10).
b15
b14 b13 b12 b11 b10
0
0
0
0
0
(3)
While Operating condition setting request (Y9) is ON, 0 is stored into A/D
conversion completed flag on all the channels.
(4)
For the read-out of digital output values, configure this area or A/D conversion
completed flag to act as an interlock.
b9
b8
0
0
0
0
0
(3) is stored into the buffer memory address 10 (Un\G10).
H
b9
b8
b7
0
0
0
0
0
0
b9
b8
b7
0
0
0
0
0
0
MELSEC-Q
b7
b6
b5
b4
b3
0
0
0
0
CH4 CH3 CH2 CH1
1 : A/D conversion completed
0 : A/D conversion in
progress or not used
b6
b5
b4
b3
b2
0
0
0
0
0
CH4 CH3 CH2 CH1
0
3
b6
b5
b4
b3
b2
0
0
0
0
0
CH2 CH1
0
2
b2
b1
b0
b1
b0
1
1
0003
(3)
H
H
b1
b0
1
0
0002
(2)
H
3 - 55

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q64ad-ghQ62ad-dgh