When User Range Setting Is Used And Initial Setting Was Made With Gx Configurator-Ad (Other System Is Available) - Mitsubishi MELSEC Q Series User Manual

Channel isolated high resolution analog-digital converter module / channel isolated high resolution analog-digital converter module (with signal conditioning function)
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

7
ONLINE MODULE CHANGE
7.3.3 When user range setting is used and initial setting was made with GX Configurator-AD
(other system is available)
7 - 14
(1) Conversion disable
(a)
Disable the conversion by the following procedures.
1)
Set the A/D conversion enable/disable setting (buffer memory address
0: Un\G0) for all channel conversion disable (F
2)
Turn on Operating condition setting request (Y9) to stop the
conversion.
3)
Operating condition setting completed flag (X9) is turned off.
4)
Check that the conversion stops with the actual analog output value.
5)
Turn off Operating condition setting request (Y9).
(The screen shows the setting example of the Q64AD-GH.)
MELSEC-Q
).
H
7 - 14

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q64ad-ghQ62ad-dgh

Table of Contents