Mitsubishi MELSEC Q Series User Manual page 63

Channel isolated high resolution analog-digital converter module / channel isolated high resolution analog-digital converter module (with signal conditioning function)
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
Device No.
Signal Name
Offset/gain
change
XC
completed flag
1
Maximum
value/minimum
XD
value reset
completed flag
A/D conversion
XE
completed flag
XF
Error flag
1: Q62AD-DGH only
3 - 34
(1) This signal is used as an interlock condition to turn ON/OFF the offset/gain change
request (YC) when the offset/gain value is changed.
(2) Refer to Section 4.6 for the offset/gain setting.
Offset/gain change completed flag
(XC)
Offset/gain change request (YC)
(1) This signal turns ON when the maximum value/minimum value stored at any of the
buffer memory addresses 30 to 37, 62 to 77 (Un\G30 to Un\G37, Un\G62 to Un\G77) is
reset when the Maximum value/minimum value reset request (YD) turns ON.
Maximum and minimum values
storage area
Buffer memory addresses 30 to 37,
62 to 77 (Un\G30 to Un\G37,
Un\G62 to Un\G77)
Maximum value/minimum value
reset request (YD)
Maximum value/minimum value
reset completed flag (XD)
(1) This turns ON when conversion for all of the channels that are conversion enabled has
been completed.
(2) For the read-out of digital output values, configure this signal or A/D conversion
completed flag (buffer memory address 10: Un\G10) to act as an interlock.
1
(3)
When the external supply power to the Q62AD-DGH switches OFF, the A/D
conversion completed flag turns OFF, the digital output values are held as previously,
and A/D conversions stop.
When the external supply power switches ON, A/D conversions resume, and as soon as
all conversion-enabled channels have completed conversions, the A/D conversion
completed flag turns ON.
The processing, such as averaging processing or primary delay filter, starts from the first
time after resumption of A/D conversion.
(1) Error flag (XF) turns ON when a write error occurs.
(2) To clear the error code, set the error clear request (YF) to ON.
Error flag (XF)
Error clear request (YF)
Description
Performed by the A/D converter module
Performed by the sequence program
Performed by the A/D converter module
Performed by the sequence program
Performed by the A/D converter module
Performed by the sequence program
The error code is read during this interval.
MELSEC-Q
3 - 34