ONLINE MODULE CHANGE
7 - 28
(4) Operation check
(a)
To make an operation check, click the [Cancel] button to cancel control
resumption.
(b)
Click the [OK] button to leave the "Online module change" mode.
(c)
Click the [Close] button to close the System monitor screen.
(d)
Set the channel for use to conversion enable in A/D conversion
enable/disable setting (buffer memory address 0: Un\G0), and then turn on
and off Operating condition setting request (Y9). Monitor the digital output
values (buffer memory addresses 11 to 14, 54 to 62, Un\G11 to Un\G14,
Un\G54 to Un\G62) to check whether proper conversion has been made or
not.