Mitsubishi MELSEC Q Series User Manual page 38

Channel isolated high resolution analog-digital converter module / channel isolated high resolution analog-digital converter module (with signal conditioning function)
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
3 - 9
(2)
Input characteristic of Q62AD-DGH
Fig. 3.3 shows a graph of the Q62AD-DGH input characteristic.
Fig. 3.3 Input characteristic of Q62AD-DGH
POINT
(1)
Set within the analog input range and digital output range for each input
range.
If these ranges are exceeded, the resolution and accuracy may not fall within
the performance specifications. (Avoid the use of dotted areas of Fig. 3.3.)
(2)
Do not input an analog input current of 0mA or less, or 30mA or more. Doing
so can cause the breakdown of the elements.
(3)
Set the offset/gain values for the user setting range within a range satisfying
the following conditions.
(a) Gain value
(b) { (gain value) - (offset value) } > 9.70mA
(4)
When an analog value that exceeds the range of the digital output value is
entered, the digital output value will be fixed at the maximum or minimum
value.
Analog input
range setting
4 to 20mA
4 to 20mA
(Extended mode)
User range setting
24mA, offset value
Digital output value (32 bits)
Minimum
Maximum
-1536
65535
-17536
73535
-1536
65535
2mA
Digital output value (16 bits)
Minimum
-768
-
-768
MELSEC-Q
Maximum
32767
-
32767
3 - 9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q64ad-ghQ62ad-dgh

Table of Contents