(2) Operating procedure
Start the settings with GX Developer I/O assignment setting screen.
(a) I/O assignment setting screen
Set the following for the slot in which the A/D
converter module is mounted.
The type setting is required; set other items as
needed.
Type
: Select "intelli."
Model name : Enter the module model name.
Points
: Select 16 points.
Start
: Enter the start I/O number for
the A/D converter module.
Detailed setting: Specify the control CPU for the
A/D converter module.
It is unnecessary to set the
"Error time output mode" or
"H/W error time PLC operation
mode" since these settings are
invalid for the A/D converter
module.
(b) Switch setting for intelligent function module
screen
Click on [Switch setting] on the I/O assignment
setting screen to display the screen shown at
left, then set switches 1 to 5.
The switches can easily be set if values are
entered in hexadecimal. Change the entry
format to hexadecimal and then enter the
values.