Siemens SIPROTEC 4 Manual page 29

Modbus tcp profile
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Selection
<see modul-specific settings>
Modbus Slave standard mapping 3-1 to
Modbus Slave standard mapping 3-n
If the mapping-file assignment was changed for a SIPROTEC 4 device, then this leads to a change of the
SIPROTEC 4 object routing to the system interface.
After assigning a new mapping-file, check the allocations to column Destination or Source in the DIGSI 4
configuration matrix.
NOTE
i
i
The mapping- file is factory-set, but you can adapt it to your device configuration.
To activate and change the protocol Modbus TCP, proceed as follows:
Activate the mapping-file Modbus Slave standard mapping 3-1 in the list box Mapping file.
²
Change the entries in the area Module-specific settings according to your device configuration.
²
Confirm with OK.
²
NOTE
i
i
Edit only the numbers in the rows which do not start with // and note the semicolons at the end of the line.
Editing anything else in the Module-specific settings may cause an error when closing the dialog Interface
Settings.
SIPROTEC 4, Modbus TCP Profile, Manual
C53000-L1840-C582-1, Edition 07.2015
Description
This selection indicates the mapping-file currently assigned to
the device with the changes of Module-specific settings already
carried out in the Module-specific settings area. Number and
version of the mapping-file have to be taken from the first line in
the Module-specific settings area.
Selection of a mapping-file 3-1 to 3-n
(n = device type dependent number of standard mappings).
All bus specific parameters are reset to default values.
Configuration in DIGSI 4
2.2 Setting the Interfaces
29