Checking the Installation

1

Checking Installation Effectiveness

No.
1
The cabinet is installed in the position specified in the engineering design documents.
2
The mechanical parts of the cabinet are installed correctly and securely, and are not
damaged. The surfaces of the cabinet do not contain any fingerprints, stains, or scratches.
3
The cable holes on the top and at the bottom of the cabinet are sealed properly.
4
The cables are routed according to the engineering design documents.
5
The cables are not damaged or broken and do not contain any joints. The cable connectors
are connected correctly and securely.
6
The labels at both ends of the cables and optical fibers are correct, legible, and in good order.
7
The optical fibers outside the cabinet are not pinched or pressed by other cables or articles
and are placed in a protective corrugated tube or cable trough.
8
The bending radius of the optical fibers is not less than 40 mm. No protruding component
exists on the routing path of the optical fibers.
9
The optical fibers are properly arranged and bound with binding straps and do not contain any
scratches.
2

Checking Equipment Prior to Powering Up

CAUTION
Ensure that fixed optical attenuators have been configured as required, before powering on the subrack.
Ensure that the circuit breaker corresponding to the idle power cable is in the "OFF" state, before powering on the equipment
Turn off the power supply facilities, and then measure the resistance between NEG(-), RTN(+), and PGND using a multimeter.
Circuit Breaker
Turn all the power switches on the
DC power distribution box to "OFF".
Turn all the power switches on the
DC power distribution box to "ON".
CAUTION
Turn off all the power switches after the measurement.
What to Check For
Resistance
Resistance Between
Between NEG(-)
NEG(-) and PGND
and RTN(+)
More than 20,000
More than 20,000
ohms
ohms
67
Method
Check the
position.
Check.
Check.
Check.
Check.
Check.
Check.
Check.
Check.
Resistance Between
RTN(+) and PGND
0
0