• Connections of the power cables between the OptiX OSN 3500 III subrack and the DC power
distribution box (N1PDU)
Power cables for the
subrack
NOTE
The maximum power consumption of the OptiX OSN 3500 III subrack is 2300 W. When the N1PDU is used, the
power consumption of the subrack cannot be more than 1100 W. Therefore, it is recommended that you select
fuses that support a maximum current of 32 A for the power supply facility.
When grounding the subrack, connect the ground bolt on the subrack to the ground point on the column inside
the cabinet. The subrack then is connected to the external ground bar through the PGND cable on the top of the
cabinet.
Ground cables of the cabinet
–48 V
–48 V
0 V
0 V
Power supply facilities in the telecommunications room
CAUTION
The power cables for the subrack are connected to the DC
power distribution box before delivery. When installing the
power cables, you can connect the power cable connectors to
the PIU board in the subrack only after changing the 3V3
connector of the power cables of the subrack to a two-hole
OT terminal. For information about how to assemble the
connector, see the "Assembling Cable Connectors" part.
35
Ground bar in the
telecommunications room