Reference operating
conditions
Maximum measured error
reference point of measurement
60 mm
50 mm
40 mm
30 mm
20 mm
10 mm
3 mm
0 mm
- 3 mm
- 10 mm
- 20 mm
- 30 mm
- 40 mm
- 50 mm
- 60 mm
100 mm
16
Performance characteristics
• Temperature = +20 °C ±5 °C
• Pressure = 1013 mbar abs. ±20 mbar
• Relative humidity (air) = 65 % ±20 %
• Metallic tank, no internals, distance to tank wall > 500 mm
• Medium: water (DC > 7), respectively oil (DC = 2)
• Probe length > 500 mm
Typical statements for reference conditions:
DIN EN 61298-2, percentage of the span.
Output:
sum of non-linearity,
non-repeatability and hysteresis
Offset / Zero
If the reference conditions are not met, the offset/zero arising from the installation setup may be up to
±12 mm. This additional offset/zero can be compensated for by entering a correction (function "offset"
(057)) during commissioning.
Differing from this, the following measuring error is present in the vicinity of the upper and lower
probe end:
200 mm
Digital
±3 mm
±4 mm
200 mm
80 mm
40 mm 20 mm
Levelflex M FMP43
Analog
±0.06 %
±0.03 %
DK = 2
(oils and solvents)
(water-based
DK > 7
medium)
(water-based
DK > 7
medium)
(
oils and solvents
DK = 2
L00-FMP43xxx-05-00-00-en-001
Endress+Hauser
)