Siemens SINAMICS G120 Function Manual page 86

Low-voltage inverter; basic positioner (epos) for cu250-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Basic positioner
3.4 Commissioning
Procedure: Fixed stop using maximum following error
To set "Travel to fixed stop" using maximum following error, proceed as follows:
1. Select "Fixed stop using maximum following error":
2. Set the following error that the inverter uses to detect the fixed stop.
3. Set the tolerance.
After the fixed stop is detected, the inverter monitors the actual position of the axis. If the
actual position value changes by more than this distance, then the converter stops the
axis and outputs fault F07484. Therefore, the converter detects that the fixed stop has
"broken away"
You have now set "Travel to fixed stop" using maximum following error.
Parameter
p2634
p2635
p2637
p2638
p2639
86
Meaning
Fixed stop, maximum following error
Fixed stop, monitoring window
Fixed stop reached
0
Fixed stop has not been reached.
1
Fixed stop has been reached.
Fixed stop outside the monitoring window
Torque limit reached
0
Torque limit has not been reached.
1
Torque limit has been reached.
Function Manual, 04/2015, FW V4.7 SP3, A5E34257659B AB