Factory Line - Wireless LAN
3-52
PHOENIX CONTACT
16 (0x10) Write Multiple Registers
3 (0x3) Read Holding Registers
Valid read requests for APs and clients for "Read Holding Registers" functions:
Current number of dialed-in stations
Table 3-3
Modbus request for the current number of dialed-in stations
Request
Function code
Starting address
Quantity of registers
Table 3-4
Modbus response for the current number of dialed-in stations
Request
Function code
Starting address
Register value
The return value corresponds to the current number of dialed-in stations with a size of
2 bytes each. A maximum of 256 stations can be included in the list. For a client, the value
is always 1.
Current receive level, transmit level, and MAC address of all dialed-in stations or of the
AP for a client.
Table 3-5
Modbus request for the current number of dialed-in stations
Request
Function code
Starting address
Quantity of registers
Table 3-6
Modbus response for the current receive level, transmit level, and MAC
address
Request
Function code
Starting address
Register value
The return value contains 8 bytes per station (4 registers wide). Bytes 1 to 6 contain the
MAC address of the station. Byte 7 contains the RSSI receive level and byte 8 contains
the current transmission power for this station.
The first 125 stations are from address 0x2 onwards, and the next 125 stations are from
address 0x80 onwards. If fewer stations are available, the registers are filled with 0x0. For
a client, there is only one value at address 0x36, which applies for the access point used.
0x03
0x2
1
0x03
0x2
2 bytes
0x03
0x3, 0x80
1 - 125 (N)
0x03
2 x N
N x 2 bytes
7190_en_02