I/O 15 Control Messages
Control Code in
Data Field in
Hex (Dec)
Hex (Dec)
0x12 (18)
00
0x13 (19)
Bit Mask
Node 0x00
0x20 (32)
through 0x38 (1–
56)
0x30 (48)
0x00 through
0x18
0x31 (49)
0x32 (50)
0x33 (51)
0x34 (52)
Example: M-GAGE Baseline
To perform a baseline function on M-GAGE Node 1, write to register 31 (the Node's register 15).
Reg 31
A baseline function on Node 1 will be initiated. (The command, both bytes together, in decimal would be 4096.)
Example: Forcing a Sample and Report
To force a sample and report of all Node 1's inputs, write the command and data to register 31.
Reg 31
The full command, both bytes together into a word, in decimal would be 4864 + 63 = 4927
Control Code and
Data Field in
Restrictions
Decimal
4608
4864
8192+Node#
Gateway Only
12288-12312
FlexPower
Devices only
12544-12586
12800-12824
13056-13080
13312-13336
0x10 (16)
0x13 (19)
www.bannerengineering.com - Tel: +1.763.544.3164
®
Sure Cross
Radio Networks and Host Controller Systems
Description
Host Communication Timeout. Set all outputs on this device to
default states. The Host Link Failure flag must be set to enable
this feature.
Force device sample and report of selected enabled inputs. The
bit mask defines which I/O point will be sampled. Bit 0 = I/O 1, Bit
1 = I/O 2, etc. A value of 0x3F (63) selects all inputs.
Enable Site Survey between Gateway and Node defined by the
data field. All error messages from the Gateway are ignored when
running Site Survey. Only one Node can participate in Site Survey
at any given time. To disable the Site Survey, use control code
0x20 with Node 0. A Node must be enabled to run the Site
Survey, then disabled before selecting the next Node.
Enable all switched power outputs. The data field selects the
voltages.
0x00 = turn off
0x05 = 5V
0x07 = 7V
0x0F = 15V
0x14 = 20V
0x18 = 24V
®
Enable switched power #1, data field selects the voltage (See
above)
Enable switched power #2, data field selects the voltage (See
above)
Enable switched power #3, data field selects the voltage (See
above)
Enable switched power #4, data field selects the voltage (See
above)
0x00
0x3F
17