Faults; Error Messages - AEG PROTECT 1 Series Operating Instructions Manual

Table of Contents

Advertisement

8.2

Faults

PROTECT 1. outputs detailed error messages by means of
which you or the service personnel can quickly and accurately
localise and interpret any malfunctions that occur. You can find
suggestions for action / solutions in the following to correct
problems using error descriptions according to chapter 8.1.2:
8.2.1

Error Messages

Message / display
No display, no acoustic
signal although system
is connected to the
mains current supply.
Mains OK, but UPS
does not switch to
bypass
"Line" LED flashes and
"Battery" LED lights up
"Inverter" LED and
"Battery" LED light up.
The acoustic signal
sounds every 4 seconds
(operating states 7-10).
"Inverter"
"Battery" LED light up.
The
sounds
(operating state no. 6).
"Fault" LED lights up,
warning signal sounds
twice per second (error
descriptions no. 12/13).
LED
and
acoustic
signal
every
second
Cause
Mains and/or
battery voltage not
in tolerance range,
poss. totally
discharged battery.
PositionMains input
use is in "OFF"
position
Mains voltage
and/or mains
frequency are
outside of tolerance
Mains voltage
supply interrupted.
Automatic
switchover to
battery mode.
Overload of the
UPS System.
52
Solution
Check mains connection
again. Check the back-
up fuse and the mains
input miniature circuit
breaker as well.
Switch mains input
miniature circuit breaker
to "ON"
Check the mains
(voltage, frequency)
Try to re-establish the
mains voltage (poss.
fuse triggered in the
subdistribution?).When
the acoustic signal
sounds every second,
the battery is almost
completely discharged.
Carry out a system
shutdown of your IT
equipment at this point
in time at the latest.
Immediately reduce the
capacity utilisation of the
UPS by disconnecting
part of your loads.