2 Mechanical Installation

2
Mechanical Installation
 Installation Environment
For optimum performance life of the drive, install the drive in an environment that meets the conditions listed below.
Environment
Installation Area
Ambient Temperature
Storage Temperature
Surrounding Area
Altitude
Vibration
Orientation
NOTICE: Never allow a constant stream of the solvent or chemicals listed above to be sprayed directly onto the drive.
 Installation Orientation and Spacing
Always install the drive in an upright position. Leave space around the unit for proper cooling as shown in the figure on the right.
Note:
V1000 Series IP66 Type should not be installed using the Side-by-Side method possible with other models.
EN 8
Indoors
-10C to +40C
Drive reliability improves in environments without wide temperature fluctuations.
-20C to +60C
Temperature conditions allowable for short-term transport.
Install the drive in an area free from:
• oil mist
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases
• excessive vibration
• direct sunlight
The surrounding area can contain the following chemicals and solvents.
(Reagent)
• Hydrochloric acid (10%)
• Sulfuric acid (10%)
• Nitric acid (10%)
• Ammonia water
• Sodium chloride
1000 m or less
10 - 20 Hz at 9.8 m/s
2
, 20 - 55 Hz at 5.9 m/s
Install the drive vertically to maintain maximum cooling effects.
30mm
V 1000
IP6 6
.
Conditions
(Solvent)
• Methanol
• Ethanol
2
30mm
100mm
Air
100mm
Air
YASKAWA Europe TOEP C710606 75B - AC Drive V1000 IP66 - Quick Start Guide