YASKAWA CIMR-VC*****H**-00 series Quick Start Manual page 23

Ip66 type. compact vector control drive

Advertisement

Par.
Name
Motor Line-to-
Sets the phase-to-phase motor resistance in
E2-05
Line Resistance
ohms. Automatically set by Auto-Tuning.
Sets the voltage drop due to motor leakage
Motor Leakage
E2-06
inductance as a percentage of motor rated
Inductance
voltage. Automatically set by Auto-Tuning.
Digital Input Settings
Digital Input S1
H1-01 to
to S6 Function
Selects the function of terminals S1 to S6.
H1-06
Selection
Major functions are listed at the end of the table.
Digital Output Settings
Digital Output
Set the function for the relay output MA-MB-
H2-01
MA/MB
MC.
Function
Digital Output P1
H2-02
Sets the function for the photocoupler output P1.
Function
Digital Output P2
H2-03
Sets the function for the photocoupler output P2.
Function
Major functions are listed at the end of the table.
Analog Input Setting
A1 Signal Level
0: 0 to +10 V (neg. input is zeroed)
H3-01
Sel.
1: 0 to +10 V (bipolar input)
H3-02
A1 Function Sel. Assign a function to terminal A1.
H3-03
A1 Gain
Sets the input value in % at 10 V analog input.
H3-04
A1 Bias
Sets the input value in % at 0 V analog input.
0: 0 to +10 V (neg. input is zeroed)
A2 Signal Level
1: 0 to +10 V (bipolar input)
H3-09
Selection
2: 4 to 20 mA (9 bit input)
3: 0 to 20 mA
H3-10
A2 Function Sel. Assign a function to terminal A2.
Sets the input value in % at 10 V/20 mA analog
H3-11
A2 Gain
input.
Sets the input value in % at 0 V/0 mA/4 mA
H3-12
A2 Bias
analog input.
Analog Input Setting
AM Monitor
Enter value equal to U1-monitor values.
H4-01
Selection
Example: Enter "103" for U1-03.
Sets terminal AM output voltage equal to 100%
H4-02
AM Gain
monitor value.
Sets terminal AM output voltage equal to 0%
H4-02
AM Bias
monitor value.
Pulse Input Setting (Frequency Reference Input)
Sets the number of pulses (in Hz) that is equal to
H6-02
RP Input Scaling
100% input value.
Pulse Train Input
Sets the input value in % at pulse input with H6-
H6-03
Gain
02 frequency.
Pulse Train Input
Sets the input value in % at 0 Hz pulse input
H6-04
Bias
frequency.
Pulse Output Setting
Enter value equal to U-monitor values.
H6-06
MP Monitor Sel.
Example: Enter "102" for U1-02.
MP Monitor
Sets the number of output pulses when the
H6-07
Scaling
monitor is 100% (in Hz).
Motor Overheat Protection
Sets the motor overload protection.
0: Disabled
Motor Overload
L1-01
1: Standard fan cooled motor
Prot. Sel.
2: Standard blower cooled motor
3: Vector motor
Motor Overload
Sets the motor overload protection time in min.
L1-02
Prot. Time
Normally no change is necessary.
Stall Prevention
0: Disabled - Motor accelerates at active
acceleration rate and may stall with too heavy
Stall Prevention
load or too short accel time.
L3-01
Selection during
1: General Purpose - Hold acceleration when
Acceleration
current is above L3-02.
2: Intelligent - Acceleration in the shortest
possible time.
YASKAWA Europe TOEP C710606 75B - AC Drive V1000 IP66 - Quick Start Guide
Description
Par.
Name
Stall Prev. Level
Sets the current level for stall prevention during
L3-02
during Accel.
acceleration.
0: Disabled - Deceleration as set. OV might
Stall Prev.
occur.
L3-04
Selection during
1: General Purpose - Deceleration is hold if DC bus
Decel.
voltage rises high.
Stall Prev.
0: Disabled - Motor stall or overload might
L3-05
Selection during
occur.
Run
1: Decel Time 1 - Reduce speed using C1-02.
Stall Prev. Level
Sets the current level at which stall prevention
L3-06
during Run
during run starts to operate.
Auto-Tuning
0: Rotational Auto-Tuning
Auto-Tuning
2: Terminal resistance only
T1-01
Mode Selection
3: Rotational Auto-Tuning for
Energy Saving
T1-02
Rated Power
Sets the motor rated power (kW).
T1-03
Rated Voltage
Sets the motor rated voltage (V).
T1-04
Rated Current
Sets the motor rated current (A).
T1-05
Base Frequency
Sets the motor base frequency (Hz).
T1-06
Motor Poles
Sets the number of motor poles.
T1-07
Base Speed
Sets the motor base speed (RPM).
Iron loss for determining the Energy Saving
T1-11
Motor Iron Loss
coefficient. If unknown leave it on default.
Monitor
U1-01
Frequency Reference (Hz)
U1-02
Output Frequency (Hz)
U1-03
Output Current (A)
U1-05
Motor Speed (Hz)
U1-06
Output Voltage Reference (Vac)
U1-07
DC Bus Voltage (Vdc)
U1-08
Output Power (kW)
U1-09
Torque Reference ( of motor rated torque)
Input Terminal Status
Reserved
U1-10
Output Terminal Status
Reserved
U1-11
Drive Status
U1-12
U1-13
Terminal A1 input level
U1-14
Terminal A2 input level
U1-16
Soft Starter Output (freq after accel/decel ramps)
U1-18
OPE Fault Parameter
6 Parameter Table
Description
Description
: ON
: OFF
1: Digital input 1
(terminal S1 enabled)
1: Digital input 2
(terminal S2 enabled)
1: Digital input 3
(terminal S3 enabled)
1: Digital input 4
(terminal S4 enabled)
1: Digital input 5
(terminal S5 enabled)
1: Digital input6
(terminal S6 enabled)
: ON
: OFF
1: Relay Output
(terminal MA-MC closed
MB-MC open)
1: Open Collector Output 1
(terminal P1) enabled
1: Open collector Output 2
(terminal P2) enabled
1: During run
1: During zero-speed
1: During REV
1: During fault reset
signal input
1: During speed agree
1: Drive ready
1: During alarm detection
1: During fault detection
EN 23