Chapter 5 Function code table
Sleep setting
P41.01
value by
frequency
Wake up
P41.02
threshold by
frequency
When selecting frequency sleep and frequency wake-up, it must be set by P41.01 < P41.02. When the frequency
source is PID setting, and the frequency wake-up must be set to PID shutdown operation: P40.39 = 1.
Sleep setting
P41.03
value by
pressure
Wake up
P41.04
threshold by
pressure
P41.05
Sleep delay time
Wake up delay
P41.06
up
Sleep
P41.07
decelerating
time
PLC current
r42.00
running mode
PLC current
r42.01
running
remaining time
PLC times of
r42.02
cycles
Simple PLC
P42.03
running mode
VFD500 high performance vector control frequency inverter user manual
0.00Hz~600HZ,It will sleep if value is less
than this value
0.00hz~600.00hz, ,It will wake up if value is
bigger than this value
0~100.0%
0.~100.0%
0.0s~6000.0s
0.0s~6000.0s
0.00(coast to stop)~60000s
Setting value decide by P03.16
P03.16 = 2, 0.00~600.00s;
P03.16 = 1, 0.0s~6000.0s;
P03.16 = 0, 0s~60000s
P41.07 set to 0,sleeping stop mode to free
coast。

42 Group Simple PLC

Read only
Read only
Read only
Unit'digit:Running mode
0: single cycle then stop
1: single cycle then keep last speed
2: recycle
3: Plc reset when single cycle stop
Ten's digit:saving selection at power off
0:power off without saving 1:power off with
saving
Hundred'digit:power save selection at stop
0:stop without power saving 1:stop with
saving
- 79-
0.00Hz
0.00Hz
0.0%
0.0%
0.0s
0.0s
0.00s
-
-
-
003