07 Group Digital Output - Veikong VFD500 Series Operation Manual

High performance vector and torque
Hide thumbs Also See for VFD500 Series:
Table of Contents

Advertisement

Chapter 5 Function code table
P06.32
DI terminal on/ready time
r07.00
DO output port status
DO1 Output terminal
P07.01
function group
DO2(HDO) Output
P07.02
terminal function group
Relay 2 Output terminal
P07.03
function group(T1A T1B
T1C)
Relay 2 Output terminal
P07.04
function group(T2A T2B
T2C)
VDO1(virtual DO1) output
P07.09
Terminal function
VFD500 high performance vector control frequency inverter user manual
When command is terminal ,power on and
terminal effective, inverter will not run ,so need
terminal ineffective then effective,then inverter
will run
0.000s~30.000s

07 Group Digital output

Define as per bit,
0:ineffective 1:effective
Bit0:DO1 Bit1:D02 Bit2:relay1, Bit 3:relay 2 Bit4:
DO3;Bit5: DO4 Bit6: DO5; Bit7: DO6
Bit8: VDO1;Bit9: VDO2
0:no function
1:READY
2:RUN
3:Error1(stop fault)
4:Error2(same as Error1 except undervoltage)
5:warning output(fault but in running)
6:swing frequency limit
7:torque limit
8:reverse running
9: upper limit frequency arrival
10:lower limit frequency arrival 1
11: lower limit frequency arrival2
12:FDT1 output frequency detection range
13:FDT2 output frequency detection range
14:setting frequency arrival
15:Desired frequency attained 1 P08.05
16:Desired frequency attained 2P08.07
17:zero speed (stop without output)
18: zero speed (stop with output)
19:zero current status
20:output current exceed limit
21:counter 1 setting value arrival
22:counter 1 setting value arrival
23:Simple PLC cycle finish
24:IGBT temperature arrival
25:Drive overload pre-warning
26: motor overload pre-warning
27: motor overheat pre-warning
28:in off loading
29:Accumulated on power time arrival
30:Accumulated running time arrival
- 47-
1.000s
-
0
0
3
0
0