Veikong VFD500 Series Operation Manual page 34

High performance vector and torque
Hide thumbs Also See for VFD500 Series:
Table of Contents

Advertisement

Chapter 5 Function code table
Functio
Parameter name
n code
P01.08
Upper limit frequency
P01.09
Lower limit frequency
Action when set
P01.10
frequency lower than
lower limit frequency
Delay time when set
P01.11
frequency lower than
lower limit frequency
Jump frequency start up
P01.12
protection
Jump frequency 1 lower
P01.13
limit
Jump frequency upper
P01.14
limit
Jump frequency 2 lower
P01.15
limit
Jump frequency 2 upper
P01.16
limit
Jump frequency 3 lower
P01.17
limit
Jump frequency 3 upper
P01.18
limit
Risk speed or Jump frequency start up protection is used to some situation which need avoid motor speed and
speed range,for example,due to mechanical resonance ,P01.12 will be enabled to avoide risk speed in forward or
reverse mode
Motor frequency
P01.18
P01.17
P01.16
P01.15
P01.14
P01.13
Multiple speed reference
P01.19
source
VFD500 high performance vector control frequency inverter user manual
Lower limit frequency(P01.09)~maximum
frequency (P01.06)
0.00Hz~upper limit frequency
0:Run at low limit frequency
1:Stop after delaying P01.11
2:Run at zero speed
0.000s~30.000s
Unit/ten/hundred'digit:three jump frequency
1/2/3
0:Disable
1:Enable (avoid risk speed)
0.00Hz~(P01.14)
P01.13- (P01.06)Maximum frequency
0.00Hz~(P01.16)
P01.15~maximum frequency(P01.06)
0.00Hz~(P01.18)
P01.17~maximum frequency(P01.06)
Giving frequency
Unit'digit:0 phase reference source
set by
0-multiple speed(P01.21)
1-preset frequency (P00.07)
2:AI1
- 31-
Description
Default
Property
50.00Hz
0.00Hz
0
0.000s
000
0.00Hz
0.00Hz
0.00Hz
0.00Hz
0.00Hz
0.00Hz
00