24 Group Motor Protection Parameter - Veikong VFD500 Series Operation Manual

High performance vector and torque
Hide thumbs Also See for VFD500 Series:
Table of Contents

Advertisement

Chapter 5 Function code table
Motor overload protection
P24.00
gain
Motor overload starting
P24.01
current at zero speed
Motor overload starting
P24.02
current at Rated speed
80min
64min
30min
5min
160s
Left: Motor overload protection starting current
Motor overload Overload protection of motor 2 only when P24.04 bits equals one or overload protection of
motor 1 or P24.08 bits equals one. P24.00 is used to adjust the overload inverse time curve time, as shown in
the right figure above, the minimum motor overload time is 5.0s.
Note: Users need to correctly set the three parameters of P24.00, P24.01 and P24.02 according to the actual
overload capacity of the motor. If set unreasonable, prone to motor overheating damage and the inverter is not
timely warning of the danger of protection.
Motor 1 protection
P24.04
option
VFD500 high performance vector control frequency inverter user manual

24 Group motor Protection parameter

0.20~10.00
50.0%~150.0%
50.0%~150.0%
Motor in self cooling mode, heat
dissipation is poor when in low
frequency but good in condition of high
frequency . P24.01 adn P24.02 is used to
set the starting point of zero and rated
speed overload current in order to
obtain a more reasonable under
different speed overload protection
Time curve
Motor overload protection
starting current
P24.02
P24.01
0
Overload
time
Overload gain P24.00=1.20
Overload gain P24.00=1.00
Overload gain P24.00=0.80
5
s
100%
120%
140%
* Overload protection starting current
Unit'digit:motor protection selection
0:No
1:overload protection(motor 1)
2:PTC1000
3:PTC100
Motor output
frequency
Fn
160%
180%
200%
220%
Right: Motor Overload Protection Curve with Different
Overload Protection Gains
- 67-
1.00
100.0%
115.0%
01