4.4 Test run

Please follow the procedure below to commission the first power-on。
Follow the instructions in Chapter 3 to install the inverter and wire it
Make sure the power cable, motor cable and brake unit are connected
Observe the safety precautions and switch on the power supply
Set each parameter in turn according to the
guidance of the wizard, set the motor self-
learning mode P11.10, press the run button,
waiting for the complete of self-learning
Open control
· Press "RUN"to Run inverter
· Press "STOP" to stop inverter
While monitoring the output frequency
or command frequency,press
"ENTER"to modify the target
frequency
Symbol
tUnE
Motor parameter self-learning
bUSY
Processing parameter read and write requests
• Indicates that the parameters have been changed
End
and saved to the EEPROM
• The mission has been completed
• Fault code, "XXX" is the fault type, see Chapter 6 for
Er.xxx
details
start
correctly
Enter guide mode"-GdE-"
N
Y
End

4-3Trial run flow chart

Meaning
close loop vector control(VC),Before normal
operation, ensure that the encoder P10.03 is in
the correct directionIf rotary self-learning is
performed, the encoder orientation can be
automatically recognized and storedIf it is not
executed, it needs to open the loop control to
run the motor and observe whether the encoder
feedback(r10.12) is in the same direction with
the given direction, if no,change as P10.03