Page 1
118965-P1 Preliminary, 5/02 MKS Type 651D Pressure Controller...
Page 2
MKS Instruments, Inc. ® Baratron is a registered trademark of MKS Instruments, Inc., Andover, MA This manual is for firmware version: pre-release...
Table of Contents Table of Contents Safety Information........................1 Symbols Used in This Instruction Manual ..............1 Symbols Found on the Unit..................2 Safety Procedures and Precautions ................3 Chapter One: General Information..................5 Introduction .......................5 How This Manual is Organized...................6 Customer Support ......................7 Chapter Two: Installation.......................9 How To Unpack the Type 651 Unit................9 Unpacking Checklist ..................9 Product Location and Requirements ................10...
Page 4
Table of Contents RS-232 Serial Interface Connector..............20 Interface (I/O) Connector ................21 Transducer Connector ................... 23 Valve Connector.................... 24 Chapter Three: Overview ...................... 25 Control Mode......................25 Gain and Phase....................25 Set Points........................28 Softstart Rates......................28 Process Limit Relays ....................29 Front Panel Components....................
Page 5
Table of Contents Labels.........................37 Voltage and Fuse Label..................37 Serial Number Label ..................37 Attention Label ....................37 Chapter Four: Local Operation....................39 General Information ....................39 Startup........................40 Optional Valve Failsafe Battery Back-Up ............40 How To Check the Battery Voltage ..............42 Setup..........................43 How to Select and Calibrate the Valve............43 How To Set the Operating Parameters............43 How To Adjust the Set Point Parameters............51 Operation ........................59...
Page 6
Table of Contents How To Set the Backfill Threshold Pressure Value........77 How To Set the Valve Position Signal Output Range........77 How To Set the Valve Battery Back-Up Control ..........77 How To Read the Sensor Type..............79 How To Set the Sensor Signal Input Range ........... 80 How To Set the Sensor Range ...............
Page 7
Table of Contents How To Select the Digital Input Functions ..............111 How To Set the Analog Set Point Inputs ............113 Digital Input Priorities..................114 How To Select the Digital Output Functions...............115 How To Activate the Softstart Rate................117 Chapter Seven: Maintenance and Troubleshooting..............119 General Information ....................119 Maintenance .......................119 How to Replace the Fuses ................119...
Page 9
List of Figures List of Figures Figure 1: Preferred Method To Connect an Overall Metal Braided Shielded Cable....15 Figure 2: Alternate Method To Connect an Overall Metal Braided Shielded Cable ....15 Figure 3: Line Voltage Selector ....................17 Figure 4: Gain Set Too High....................
Page 11
Safety Information Symbols Used in This Instruction Manual List of Tables Table 1: Definition of Symbols Found on the Unit..............2 Table 2: Transducer Current Available................... 11 Table 3: System Interface Cables.................... 12 Table 4: Adapter Cables ......................13 Table 5: Power and Fuse Requirements ................. 16 Table 6: Rear Panel Connector Slot Labels................
Safety Information Symbols Used in This Instruction Manual Safety Information Symbols Used in This Instruction Manual Definitions of WARNING, CAUTION, and NOTE messages used throughout the manual. Warning The WARNING sign denotes a hazard. It calls attention to a procedure, practice, condition, or the like, which, if not correctly performed or adhered to, could result in injury to personnel.
Symbols Found on the Unit Safety Information Symbols Found on the Unit The following table describes symbols that may be found on the unit. Definition of Symbols Found on the Unit Protective earth (ground) Earth (ground) Off (Supply) On (Supply) IEC 417, No.5017 IEC 417, No.5019 IEC 417, No.5008...
DO NOT SUBSTITUTE PARTS OR MODIFY CONTROLLER Do not install substitute parts or perform any unauthorized modification to the controller. Return the controller to an MKS Calibration and Service Center for service and repair to ensure that all safety features are maintained.
Page 16
Safety Procedures and Precautions Safety Information USE THE PROPER POWER SOURCE This product is intended to operate from a power source that does not apply more voltage between the supply conductors, or between either of the supply conductors and ground, than that specified in the manual.
651 controller. The 100° C temperature-controlled, linear Baratron transducers are compatible with the high power unit. Refer to Product Compatibility, page 11, for a complete listing of the MKS products that are compatible with the 651 controller.
How This Manual is Organized Chapter One: General Information How This Manual is Organized This manual is designed to provide instructions on how to set up, install, and operate a Type 651 unit. Before installing your Type 651 unit in a system and/or operating it, carefully read and familiarize yourself with all precautionary notes in the Safety Messages and Procedures section at the front of this manual.
Calibration and Service Center before shipping. The ERA Number expedites handling and ensures proper servicing of your controller. Please refer to the inside of the back cover of this manual for a list of MKS Calibration and Service Centers. Warning All returns to MKS Instruments must be free of harmful, corrosive, radioactive, or toxic materials.
Page 20
Customer Support Chapter One: General Information This page intentionally left blank.
Chapter Two: Installation How To Unpack the Type 651 Unit MKS has carefully packed the Type 651 unit so that it will reach you in perfect operating order. Upon receiving the unit, however, you should check for defects, cracks, broken connectors, etc., to be certain that damage has not occurred during shipment.
Includes an I/O connector for the rear panel of the unit, a cover for the I/O connector, and a screwlock assembly for the I/O connector cover • MKS Type 253 (fast or standard) or 653 control valve • Valve Failsafe Battery Back-Up (factory installed) •...
Chapter Two: Installation Product Compatibility Product Compatibility Valves MKS downstream control valves compatible with the 651 unit include: • Types 253 and 653 Transducers MKS transducers compatible with the low power 651 unit include: • Types 121, 122, 124, 127, 128 , 220, 223, 622, 626, 627, and 628.
January 1, 1997, some products shipped to the European Community must also comply with the Product Safety Directive 92/59/EEC and Low Voltage Directive 73/23/EEC, which cover general safety practices for design and workmanship. MKS products that meet these requirements are identified by application of the CE mark.
Type “D” connectors on the 651 controller to your unit. The required adapter cables are listed in Table 4. Adapter Cables From Use the MKS Cable... Standard Shielded 651 I/O...
Chapter Two: Installation Generic Shielded Cables MKS offers a full line of cables for all MKS equipment. Should you choose to manufacture your own cables, follow the guidelines listed below: 1. The cable must have an overall metal braided shield, covering all wires. Neither aluminum foil nor spiral shielding will be as effective;...
Chapter Two: Installation Interface Cables Example 1: Preferred Method To Connect Cable (shown on a transducer) Metal Cable Clamp Screw Transducer Split Lock Washer Overall Insulation External Tooth Lock Washer (if present) Bare Metal Cable Clamp Transducer Housing Making Firm Contact To Braid Braid Here Is Desirable Optional Plastic or Metal Cable (but not usually necessary)
Setup Chapter Two: Installation Setup Mounting Instructions The 651 unit can be mounted in either a panel cutout or in one of the rack mount options (refer to Optional Equipment, page 10). Position the unit with proper clearance, to allow air cooling, so that the unit can operate within the specified temperature range.
Chapter Two: Installation Setup Grounding For protective earthing, plug the power cord into a properly grounded outlet. How To Set the Line Voltage The line voltage selector, located on the rear panel of the 651 unit (refer to Figure 9), configures the 651 unit to accept either 115 or 230 VAC input voltage The Line Voltage Selector on the 651 unit must be set to the proper Caution...
Page 30
Setup Chapter Two: Installation Warning Be sure that your 651 unit is plugged into the correct AC outlet for the selected line voltage. Plugging a unit with 115V line voltage into a 230 V outlet will damage the controller!
Chapter Two: Installation Connectors Connectors Rear Panel Connectors The 651 controller has five Type “D” connectors on its rear panel (refer to Figure 9, page 32). The connectors are numbered, from right to left as 1 to 4, as listed in Table 6. Rear Panel Connector Slot Labels Slot Number Type “D”...
The 9-pin male Type “D” Serial Interface connector is used to connect the 651 unit to a computer, providing an interface for RS-232 communications. Caution You must use the MKS cable CB651S-10-10 to make the connection from the 651 unit’s 9-pin serial port to a computer’s 9-pin serial port.
Chapter Two: Installation Connectors Interface (I/O) Connector The 37-pin female Type “D” Interface (I/O) connector provides access to the set points, process relay limits, softstart control, and the valve control functions. Interface Connector Pinout Pin Number Assignment Pin Number Assignment PLO 1 - NC contact PLO 1 - common contact PLO 1 - NO contact...
Connectors Chapter Two: Installation transducer, connect the negative analog set point (pin 34) to analog ground (pin 35). Table 8: Interface Connector Pinout...
Chapter Two: Installation Connectors Transducer Connector The 15-pin female Type “D” connector is used to connect the 651 unit to a transducer. The upper, 15-pin ‘D’ connector, is for the High Range pressure sensor. The lower, 15-pin Hi-Density ‘D’, is for the Low Range pressure sensor Both pressure sensor connectors use the same pinout shown below.
Connectors Chapter Two: Installation Valve Connector The 9-pin female Type “D” Valve connector allows you to connect the 651 controller to either a 653 or 253 throttle valve. Valve Connector Pinout Pin Number Assignment Motor winding A low Motor winding A high Limit switch ground Open limit switch signal Closed limit switch signal...
Chapter Three: Overview Control Mode Chapter Three: Overview Control Mode The 651 controller can control a vacuum system using the PID control mode. In the PID mode, the 651 controller uses a Proportional, Integral, and Derivative (PID) algorithm for control, which requires you to input two (gain and phase) values. Each set point uses its own gain and phase value to optimize the response from set point to set point.
Control Mode Chapter Three: Overview Phase The phase provides a control signal that is proportional to the integral of the error signal. This phase is responsible for allowing the controller to track the set point with zero steady state error. If the phase is too low, the pressure will overshoot the set point before settling in (refer to Figure 5).
Chapter Three: Overview Control Mode Gain Gain provides a control signal that is directly proportional to the error signal. The error signal is the difference between the actual pressure and the set point. This gain is responsible for controlling how quickly the pressure responds to a change in set point. A large gain generally results in a faster response to set point.
Set Points Chapter Three: Overview Set Points The 651 controller has five internal set points (A to E) and is capable of accepting one analog set point through the Interface connector on the rear panel. The unit controls the system based on the value of the “active”...
Chapter Three: Overview Process Limit Relays Process Limit Relays There are two process limit (PLO) relays in the 651 controller. Each relay has a high and a low trip limit. Refer to Table 8, for the Interface connector pinout, to determine which pins are for relay 1, and which are for relay 2.
Front Panel Components Chapter Three: Overview Front Panel Components Valve Position Control Keys Display Window Type 651 Pressure Controller Point Set Point Selection Valve Stop Keys Remote Parameters Learn Open Local Zero Close Select Adjust Key Lock Arrow Keys Adjust Sensor Learn Switch...
Chapter Three: Overview Front Panel Components Arrow Keys The up arrow key [ ] is used to display the next screen in the open menu. The down arrow key [ ] is used to display the previous screen in the open menu. Adjust Knob The adjust knob, which turns clockwise and counterclockwise, is used to select a parameter value.
Chapter Three: Overview Line Voltage Selector Switch This switch sets the unit to operate at either 115 VAC or 230 VAC. Refer to How To Set the Line Voltage, for more information. Fuse Holder This housing holds the unit’s two fuses. The fuse values are listed in Table 5, page 16. Refer to How to Replace the Fuses, page 127, for more information.
When in a disabled state, backup power is not provided. In most cases this means that the value doesn’t move, but this is not guaranteed. This battery is a rechargeable, 12 Volt, 2 amp-hour, sealed lead-acid battery (MKS part no. 003-1109451). If the battery backup is installed, an...
Chapter Three: Overview Optional Valve Failsafe Battery Back-Up If for any reason the controller cannot open or close the valve within 30 Note seconds of a power failure, the battery back-up module automatically turns off. This prevents the battery from discharging when no valve is present or if the valve is defective in some way.
Optional Valve Failsafe Battery Back-Up Chapter Three: Overview Battery Storage The lead-acid battery loses its capacity if it is stored with no power connected. In fact, the higher the ambient temperature, the faster the capacity is lost. Table 12 lists the time it takes for the battery to fall to fifty percent of its full capacity at various ambient temperatures.
CE mark signifying compliance with the European CE regulations. Serial #: 0123456789 Model #: 651DXYZCD MKS Instruments, Inc. Made in the USA Figure 11: Serial Number Label The model code is identified as “651DXYZCD.” Refer to Appendix B: Model Code Explanation, page 133, for more information.
Page 50
Labels Chapter Three: Overview This page intentionally left blank.
Chapter Four: Local Operation General Information Chapter Four: Local Operation General Information Local operation of the 651 controller is achieved by using the controls on the front panel of the controller. There are three main software menus, accessed through the front panel that allow you to configure the system.
Startup At initial power up, the display screen appears for about five seconds, listing the current software/firmware version (refer to Figure 12). MKS TYPE 651D V 1.0 Figure 12: Initial Display Screen The system then advances to its default Pressure and Position display (refer to Figure 13) and is ready for valve connection and setup (or normal operation once the system has been configured).
Chapter Four: Local Operation Startup Battery Voltage Out-of-Range If the battery voltage is out-of-range, the controller revision and the current software/firmware version appear on the front panel display for about five seconds (refer to Figure 12), followed by the appropriate error message, rather than advancing to the default Pressure and Position display screen).
Startup Chapter Four: Local Operation How To Check the Battery Voltage Note Refer to Optional Valve Failsafe Battery Back-Up for more information. To be sure that the 651 unit has recognized the optional battery back-up module, or to view the actual battery voltage and the current valve configuration without entering the software menus (regardless of whether you are using Local or Remote operation): 1.
Chapter Four: Local Operation Setup Setup How to Select and Calibrate the Valve The 651 controller works with the 253 or 653 valve. Choose the appropriate valve and connect it to the 651 unit (refer to the valve manual if necessary). Caution The procedure for calibrating (learning) the valve involves cycling the valve from the open to the close position.
Page 56
Setup Chapter Four: Local Operation Settings stored in non-volatile RAM are saved when the power is turned off. When the power is restored, the 651 unit “remembers” the latest configuration, not the initial configuration. To enter the Setup Menu to configure the operating parameters: 1.
Page 57
Chapter Four: Local Operation Setup 4. Press the [ ] key to advance to the next screen. The screen displays: DELIMITER: CRLF Select the delimiter from the options of CRLF (carriage return/line feed - initial) or CR (carriage return). 5. Press the [ ] key to advance to the next screen.
Setup Chapter Four: Local Operation Full Scale Sensor Ranges Torr mBar .10000 .20000 .5000 1.0000 1.3332 2.0000 2.6664 5.000 10.000 13.332 20.000 50.00 100.00* 133.32 200.00 500.0 1000.0 1333.2 5000 6666 10000 13332 *Initial setting Table 13: Full Scale Sensor Ranges To view the range of a sensor in pressure units of mBar for a sensor calibrated in Torr, select the equivalent mBar unit of measure.
Page 59
Chapter Four: Local Operation Setup Select the pressure units for the 651 controller display from the options of Torr (initial), mTorr, mBar, µBar, kPa, Pa, cmH O, and inH 8. Press the [ ] key to advance to the next screen. The screen displays: CHANNEL SELECT: AUTO...
Page 60
Setup Chapter Four: Local Operation 11. Press the [ ] key to advance to the next screen. The screen displays: VALVE SIGNAL OUTPUT: 10 VOLTS Select the full scale voltage range for the valve position signal (analog) output from the options of 5 Volts or 10 Volts (initial).
Page 61
Chapter Four: Local Operation Setup SOFT START RATE ANLG SETPT: 100% Set the softstart rate for the analog set point to any value from 0.1% (slowest) to 100% (fastest - initial) of full scale. If it is not necessary to use softstart control in your process, leave the softstart rate at the initial setting of 100%.
Page 62
Setup Chapter Four: Local Operation 19. Press the [ ] key to advance to the next screen. The screen displays: BATTERY 13.5V BACK-UP: OPEN Note This screen only appears if the valve failsafe battery back-up option is installed in your 651 controller. The screen displays the actual voltage level of the battery along with the position the valve is currently set to drive to upon a power loss.
Chapter Four: Local Operation Setup How To Adjust the Set Point Parameters The set point parameters include the internal set points (A to E), gains and phases, two process limit relays (each with high and low trip levels), and the external analog set point. The software menu screens for setting the set point parameters varies slightly, depending on your system’s configuration.
Page 64
Setup Chapter Four: Local Operation PID Control with Pressure Set Points To enter the Main Menu to access the set point and gain parameters: Note When using PID control, the gains can be adjusted to provide the best response to the set point. 1.
Page 65
Chapter Four: Local Operation Setup The screen displays: GAIN COMP FACTOR: 100.0 The Gain Compensation Factor (GCF) modifies the gain value so that the controller gives the best response to the low range setpoints. When the 651 controller receives a set point in the range of the High range sensor, it uses the Gain value.
Page 66
Setup Chapter Four: Local Operation BACKFILL / RELAY2: ENAB DISAB The Backfill Valve Control feature can open a pneumatic valve to assist in raising the system pressure to a new setpoint. Note: When the backfill valve control feature is enabled, process relay 2 is disabled. When backfill valve control feature is disabled, relay 2 is enabled.
Page 67
Chapter Four: Local Operation Setup Enter the Setpoint backfill limit value, range from 10 to 100 %. 10. Repeat steps 2 to 4 for set points B to E. * These menu screens only appear when Setpoint A is in Pressure control mode.
Page 68
Setup Chapter Four: Local Operation Position Set Point Control To enter the Main Menu to access the set point parameters: Note There are no gain values associated with set points under position control. 1. Be sure that the default Pressure and Position display appears on the screen. 2.
Page 69
Chapter Four: Local Operation Setup Process Limit The following series of screens are accessible by pressing the [ ] key after you have configured the set point and gain parameters (if applicable). These screens are the same regardless of your system’s configuration. Be sure that the default Pressure and Position display appears on the screen.
Page 70
Setup Chapter Four: Local Operation Note 1. To disable a low limit trip point, set it to negative full scale. 2. To disable a high limit trip point, set it to full scale. Analog Setpoint Value Be sure that the default Pressure and Position display appears on the screen. Press the [ ] key to advance to the analog setpoint screen.
Chapter Four: Local Operation Operation Operation How To Activate a Set Point Activating a set point commands the 651 unit to control to that set point. Only one set point can be active at a time. How To Activate an Internal Set Point The internal set points (A to E) are activated by pressing the appropriate key on the front panel of the 651 controller (refer to Figure 8.).
Operation Chapter Four: Local Operation How To Control the Valve The 651 unit can drive the throttle valve to full open or full close, or halt at its current position. Note The commands to open, close, or halt the valve override the active set point control of the valve.
Chapter Four: Local Operation Operation How To Use the Sensor Zero The sensor zero function corrects any sensor zero offsets. To zero the currently displayed sensor (indicated on the display by a ‘H” for the High pressure sensor or an ‘L’ for the Low pressure sensor) 1.
Page 74
Operation Chapter Four: Local Operation ZERO BASE PRESSURE: 2. Adjust the pressure reading on the display until it matches the known base pressure reading (as measured by another transducer in the system). 3. Press any key to return to the default Pressure and Position display screen.
Chapter Four: Local Operation Operation How To Remove the Zero Correction Factors This function removes the sensor and special zero correction factors stored in memory, and is used to determine the uncorrected signal from the pressure transducer. Each time a sensor is zeroed, the offset changes and the pressure display is updated.
Operation Chapter Four: Local Operation 4. Press the [L ] and [Z ] keys simultaneously for about three seconds. EARN The 651 controller learns the input voltage that corresponds to the analog set point zero value, then the screen returns to the default Pressure and Position display screen. How To Calibrate the Full Scale of the Analog Set Point The analog set point can be configured for 5 V (initial) or 10 V full scale input (refer to step 9).
Page 77
Chapter Four: Local Operation Operation 5. Adjust the value of the analog set point to 100%. The 4.5 Volt input to the Interface connector is now the full scale value. To be sure that the analog set point is adjusted correctly, turn the adjust knob until the reading flickers between 99.99 and 100.00%.
Chapter Five: Remote RS-232 Operation General Information Chapter Five: Remote RS-232 Operation General Information Remote (or rear panel) control of the 651 pressure controller is achieved either through digital RS-232 communications through the Serial Interface connector, or through analog or digital logic control at the rear panel Interface connector (refer to Table 8).
RS-232 Protocol Chapter Five: Remote RS-232 Operation RS-232 Protocol Messages sent to the 651 controller from a remote computer are either commands that instruct the controller to perform a task or change an operating parameter, or requests that prompt the controller to report information.
Chapter Five: Remote RS-232 Operation RS-232 Protocol Message Syntax The RS-232 message syntax uses the following conventions: Note 1. Commands and requests are not case sensitive. 2. Spaces are included in the syntax for clarity only. Do not include spaces in actual messages. bold Messages that you must enter exactly as shown in the manual.
Setup Messages Chapter Five: Remote RS-232 Operation Setup Messages The Setup messages configure the operating parameters for the 651 unit. Table 14 RS-232 Setup Messages Description Command Request Response J type Select and Calibrate J type R 23 the Valve 1 = Std 253 type: 1 = Std 253* type:...
Chapter Five: Remote RS-232 Operation Setup Messages Table 14: RS-232 Setup Messages (Continued) Valve Position Signal B value R 31 B value Output Range value: 0 = 5 V value: 0 = 5 V 1 = 10 V 1 = 10 V* K value Valve Battery K value...
Page 85
Chapter Five: Remote RS-232 Operation Setup Messages How To Select and Calibrate the Valve The 651 unit can control Type 253 and Type 653 valves. Be sure that the valve is connected to the 651 unit. Caution The procedure for selecting the valve involves cycling the valve from the open to the close position.
Setup Messages Chapter Five: Remote RS-232 Operation How To Read the Pressure Control Mode To query the current control mode setting, issue the request: R 51 The controller responds with the message [V value], where: value: 1 = PID...
Chapter Five: Remote RS-232 Operation Setup Messages How to Set the Pressure Units The command [F value] identifies the units for the 651 controller display, where: value: 00 = Torr (initial) 01 = mTorr 02 = mBar 03 = µBar 04 = kPa 05 = Pa 06 = cm H...
Setup Messages Chapter Five: Remote RS-232 Operation How To Enable Backfill Valve Control The Backfill Valve Control feature can open a pneumatic valve to assist in raising the system pressure to a new setpoint. The messages described here enable and disable the feature, and check which of those states is in force.
Chapter Five: Remote RS-232 Operation Setup Messages How To Set the Backfill Threshold Pressure Value This value is the required difference between the new set point and the current pressure in the system before the backfill control feature operates. Set point changes less than the backfill threshold value do not trigger the backfill function.
Page 90
Setup Messages Chapter Five: Remote RS-232 Operation = Open valve at power failure = Close valve at power failure To check the direction of the valve battery back-up control, issue the request: R 40 The controller responds with the message [K value], where: value: 0 = Option disabled = Valve opens at power failure...
Chapter Five: Remote RS-232 Operation Setup Messages How To Read the Sensor Type To query the current sensor type, issue the request: R 36 The controller responds with the message [U value], where: value: 0 = Absolute An example response is:...
Setup Messages Chapter Five: Remote RS-232 Operation How To Set the Sensor Signal Input Range Note Be sure that the sensor is connected to the 651 controller before changing the sensor signal input range. The command [G value] sets the full scale voltage range for the pressure sensor input, where: value: 0 = 1 Volt...
Chapter Five: Remote RS-232 Operation Setup Messages How To Set the Sensor Range Note Be sure that the sensor is connected to the 651 controller before changing the sensor range. The command [Ex value] identifies the range of the sensor, in units, where x corresponds to either ‘H’...
Page 94
Setup Messages Chapter Five: Remote RS-232 Operation To check the sensor range of your unit, issue the request: R 55 for the Low range sensor R 33 for the High range sensor The controller responds with the message [Ex value], where x corresponds to either ‘H’ or ‘L’...
Page 95
Chapter Five: Remote RS-232 Operation Setup Messages Set Point Messages The Set Point messages define the set point parameters which include the set point values, the gains and phases, and two process limit relays (each with high and low trip point levels). All of the set point messages (except for the gain and phase parameters) function the same, regardless of your system’s configuration.
Setup Messages Chapter Five: Remote RS-232 Operation RS-232 Set Point Messages Description Command Request Response T x value Set Point Control T x value R xx x: 0 = Analog Set Pt x: 1 = Set Point A xx: 25 = Analog Set Pt 1 = Set Point A 2 = Set Point B 26 = Set Point A...
Page 97
Chapter Five: Remote RS-232 Operation Setup Messages Description Command Request Response M x value Gain M x value R xx x: 1 = Gain SP A x: 1 = Gain SP A xx:46 = Gain SP A 2 = Gain SP B 2 = Gain SP B 47 = Gain SP B 3 = Gain SP C...
Setup Messages Chapter Five: Remote RS-232 Operation How To Set the Type of Set Point Control Each set point can be configured so that it is represents a pressure value or position value. The command [T x value] configures the unit for set point control, where: = Set point A control = Set point B control = Set point C control...
Chapter Five: Remote RS-232 Operation Setup Messages How To Set the Analog Set Point Range The command [A value] sets the full scale voltage range for the analog set point, where: value: 0 = 5 Volts (initial) = 10 Volts To query the voltage range of the analog set point, issue the request: R 24 The controller responds with the message [A range], where:...
Setup Messages Chapter Five: Remote RS-232 Operation How To Set the Set Point Values The command [S x value] sets the values for the set points, where: = Set point A value = Set point B value = Set point C value = Set point D value = Set point E value = Analog set point value...
Page 101
Chapter Five: Remote RS-232 Operation Setup Messages The controller responds with the message [S x value], where: = Analog set point value = Set point A value = Set point B value = Set point C value = Set point D value = Set point E value value: set points A to E:...
Setup Messages Chapter Five: Remote RS-232 Operation How To Set the Gain Values The command [M x value] sets the gain values for the internal set points, where: = Set point A gain = Set point B gain = Set point C gain = Set point D gain = Set point E gain value:...
Chapter Five: Remote RS-232 Operation Setup Messages How To Set the Gain Compensation Factor The gain compensation factor (GCF) modifies the gain value so that the controller gives the best response to the low range set points. When the 651 controller receives a set point in the range of the high sensor (Channel 1), it uses the gain value entered with the [Mxvalue] command.
Setup Messages Chapter Five: Remote RS-232 Operation How To Set the Phase Values The command [X x value] sets the Phase values for the internal set points, where: = Set point A Phase = Set point B Phase = Set point C Phase = Set point D Phase = Set point E Phase value:...
Chapter Five: Remote RS-232 Operation Setup Messages How To Set the Phase Compensation Factor The phase compensation factor (PCF) modifies the phase value so that the controller gives the best response to the low range set points. When the 651 controller receives a set point in the range of the high sensor, it uses the phase value entered with the [Xxvalue] command.
Setup Messages Chapter Five: Remote RS-232 Operation How To Set the Softstart Rates The softstart rate controls the rate at which flow moves toward the desired set point. Different softstart rates can be assigned to each set point as well as to the valve open and valve close commands.
Page 107
Chapter Five: Remote RS-232 Operation Setup Messages To change the softstart rate for set point A to 50% enter: I 1 50...
Setup Messages Chapter Five: Remote RS-232 Operation How To Set the Process Limit Relays The command [P x value] sets the process limit relay thresholds, where: = Low threshold - Process Limit 1 = High threshold - Process Limit 1 = Low threshold - Process Limit 2 = High threshold - Process Limit 2 value:...
Chapter Five: Remote RS-232 Operation Control Messages Control Messages The control messages directly control the actions of the valve and the system. RS-232 Control Messages Description Command Request Response x y z w Activate Set Point X: Active Set x: 1 = Set Point A Point 2 = Set Point B 3 = Set Point C...
Page 110
Control Messages Chapter Five: Remote RS-232 Operation RS-232 Control Messages Valve Stop None None • stops valve in current position Sensor Zero None None • corrects sensor zero offsets Special Zero Z 2 value None None • zeros base pressure value: % FS pressure Remove Sensor and None...
Chapter Five: Remote RS-232 Operation Control Messages How To Activate a Set Point The command [D x] activates one of the set points, where: x: 1 = Set point A = Set point B = Set point C = Set point D = Set point E = Analog set point To activate set point A, enter:...
Control Messages Chapter Five: Remote RS-232 Operation How To Control the Valve The 651 unit can drive the throttle valve to full open or full close, or to stop at its current position. There are no requests associated with these functions. Note The RS-232 commands to open, close, or stop the valve override the active set point control of the valve.
Chapter Five: Remote RS-232 Operation Control Messages How To Use the Sensor Zero The command [Z 1] corrects for any sensor zero offsets. There is no request associated with this function. This command will zero the currently selected pressure sensor range. To use the sensor zero: 1.
Control Messages Chapter Five: Remote RS-232 Operation The command [Z 3] removes the sensor zero [Z 1] and the special zero [Z2 value] correction factors stored in memory, and is used to determine the uncorrected signal from the pressure transducer. Each time a sensor is zeroed, the offset changes and the pressure display is updated.
Chapter Five: Remote RS-232 Operation Control Messages How To Calibrate the Full Scale of the Analog Set Point The analog set point can be configured for 5 Volt (initial) or 10 Volt full scale input (refer to How To Set the Analog Set Point Range). You can, however, operate the 651 controller at a different full scale input, for example, 4.5 V, by recalibrating the full scale of the analog set point.
Informational Messages Chapter Five: Remote RS-232 Operation Informational Messages Informational messages report data on the 651 controller. There are no commands associated with these functions. RS-232 Informational Messages Description Request Response P value Pressure Reading • reports pressure reading as value: % FS % of FS Valve Position Value...
Page 117
Chapter Five: Remote RS-232 Operation Informational Messages RS-232 Informational Messages (Continued) Description Request Response BT x Valve Battery Back-Up Status R 39 • reports the voltage status of x: 0 = Battery voltage is out of the optional valve failsafe range battery back-up 1 = Battery voltage is within...
Informational Messages Chapter Five: Remote RS-232 Operation How To Report the Pressure Reading To report the currently selected pressure reading as a percentage (%) of full scale (FS) of your pressure sensor, issue the request: The controller responds with the message [P value], where: value: % of sensor full scale Note Pressure readings are reported as a percentage of full scale, where full...
Chapter Five: Remote RS-232 Operation Informational Messages How To Report the Valve Position Value To report the valve position value as a percentage (%) of full Open, issue the request: The controller responds with the message [V value], where: value: % of full Open Example: if the valve is at 50, the response is: V+0050.0 The valve position is 50% of full open.
Informational Messages Chapter Five: Remote RS-232 Operation How To Report the System Status The system status request reports the type of operation, the state of the learn function, and the state of the valve control. To report the system status, issue the request: R 37 The controller responds with the message: x y z...
Chapter Five: Remote RS-232 Operation Informational Messages How To Report the Voltage Status of the Valve Battery Back-Up To report the voltage status of the optional valve failsafe battery back-up, issue the command: R 39 The controller responds with the message: BT x where x: 0 = Battery voltage is out of range...
If the checksum error persists after you perform a full system calibration, followed by a recalibration of the span of the A/D converter, the error indicates a hardware failure of the EEPROM. Contact any MKS Service Center, listed on the inside back cover of this manual, for assistance.
Chapter Six: Remote Digital Logic Control General Information Chapter Six: Remote Digital Logic Control General Information Digital and analog control of the 651 unit is accomplished via the Interface connector located on the rear panel. Refer to Table 8, for the Interface connector pinout. Note Any RS-232 command takes priority over digital logic commands.
How To Select the Digital Input Functions Chapter Six: Remote Digital Logic Control Refer to Table 8, for the complete Interface connector pinout. Digital Input Functions I/O Pin No. State Digital Input Function Analog set point to position High Analog set point to pressure Softstart is active for selected command function High...
Chapter Six: Remote Digital Logic Control How To Select the Digital Input Functions Digital Input Functions (Continued) I/O Pin No. State Digital Input Function Selects set point B High No function Selects set point A High No function No function High No function Performs the remote zero function...
How To Select the Digital Input Functions Chapter Six: Remote Digital Logic Control Digital Input Priorities Digital inputs are scanned and selected in a prioritized manner, enabling a higher priority request to override a lower one. The order of priority is shown in Table 18. Priority of Digital Inputs Order of Priority I/O Pin No.
Chapter Six: Remote Digital Logic Control How To Select the Digital Output Functions How To Select the Digital Output Functions The I/O board contains 6 type 74HC digital outputs, each having the capacity to drive one standard TTL load. The specific function of each output is listed in Table 19, page 116. The approximate time constant of the outputs are 2.5 microseconds.
How To Select the Digital Output Functions Chapter Six: Remote Digital Logic Control Refer to Table 8, for the complete Interface connector pinout. Digital Output Functions I/O Pin No. State Digital Output Function Valve is not open High Valve is open Valve is not closed High Valve is closed...
Chapter Six: Remote Digital Logic Control How To Activate the Softstart Rate How To Activate the Softstart Rate When using the front panel controls or RS-232 to Open the valve, Close the valve, or use a setpoint, the softstart rate is automatically activated. Having a softstart rate setting of 100% is the same as not applying any softstart rate.
Page 130
How To Activate the Softstart Rate Chapter Six: Remote Digital Logic Control This page intentionally left blank.
Instruments immediately. If it is necessary to return the unit to MKS, obtain an ERA number (Equipment Return Authorization Number) from a MKS Service Center before shipping. Please refer to the inside back cover of this manual for a list of MKS Calibration and Service Centers. Warning All returns to MKS Instruments must be free of harmful, corrosive, radioactive, or toxic materials.
Maintenance Chapter Seven: Maintenance and Troubleshooting Warning To avoid an electrical shock, be sure to disconnect the power cord before proceeding. 3. Disconnect all cables from the connectors located on the rear panel of the unit. 4. Insert a small device such as a screwdriver in the fuse holder clip on the right side of the fuse holder.
This memory module (MKS part no. 037-9227) is specified to provide at least seven years of memory storage under all operating conditions. Maintenance is normally not required during this period. The memory module may need to be replaced if the 651 unit continually loses set up information at each power cycle (power off then on again).
Maintenance Chapter Seven: Maintenance and Troubleshooting 7. Remove the Phillips head screw to the left of the Serial Interface connector. 8. Remove the CPU board from the 651 controller. It may be necessary to remove the clamping spring that holds the card cage to the power supply.
Page 135
Chapter Seven: Maintenance and Troubleshooting Maintenance How To Replace the CPU Board 1. Position the CPU board over slot 1 in the 651 unit, ensuring that the board’s edge is behind the next connector’s edge. 2. Push on the bottom tab to snap the board into the slot. 3.
Maintenance Chapter Seven: Maintenance and Troubleshooting How To Replace the Optional Valve Failsafe Battery Warning The 651 unit has lethal voltages inside. Only qualified personnel must perform servicing of the unit. To avoid an electrical shock, disconnect the power line before opening the unit.
Page 137
Chapter Seven: Maintenance and Troubleshooting Maintenance 14. Pull the front panel module completely forward and remove the battery circuit board assembly. 15. Disconnect the two insulated clips from the battery terminals. Caution Do not allow anything to short across the battery terminals, such as a screwdriver.
Troubleshooting Chapter Seven: Maintenance and Troubleshooting Troubleshooting How To Identify an Out-of-Range Pressure Condition An out-of-range condition occurs at ±105% of FS (±10.5 Volts at sensor input) and is displayed as a positive or negative polarity. An example of a positive out-of-range pressure condition is shown below. PRES +++++++ 0.0%...
Refer to How To Calibrate the Full Scale of the Analog Set Point, page 103. If the checksum error persists after you perform a full calibration, the error indicates a hardware failure of the EEPROM. Contact any MKS Service Center, listed on the inside back cover of this manual, for assistance.
Troubleshooting Chapter Seven: Maintenance and Troubleshooting How To Calibrate the Span of the A/D Converter The controller’s A/D (analog-to-digital) converter converts the analog input to a digital value that the controller uses. The span of the A/D converter is calibrated at the factory. However, you may need to recalibrate the span if your unit issues a checksum error when you power up the controller, or if the transducer’s readings are incorrect.
Page 141
In that case, repeat the A/D converter calibration. If the error persists, it indicates a hardware failure of the EEPROM. Contact any MKS Service Center, listed on the inside back cover of this manual, for assistance.
Page 142
Troubleshooting Chapter Seven: Maintenance and Troubleshooting This page intentionally left blank.
Appendix A: Product Specifications Appendix A: Product Specifications Ambient Operating Temperature Range 15° to 40° C (59° to 104° F) 15° to 35° C (59° to 95° F) with the optional valve failsafe battery backup Analog Output Signal Position 0 to 5 Volts or 0 to 10 Volts, selectable Pressure 110% FS pressure, same range as sensor CE Mark Compliance...
Page 144
Appendix A: Product Specifications External Set Point Signal 5 Volts or 10 Volts*, selectable Fuses Low power unit: 90 to 132 VAC 0.63A (T), 250V, 5 x 20 mm 180 to 264 VAC 0.315A (T), 250V, 5 x 20 mm High power unit: 90 to 132 VAC 1.25A (T), 250V, 5 x 20 mm 180 to 264 VAC...
Appendix B: Model Code Explanation Appendix B: Model Code Explanation Model Code The desired options for the 651 controller are identified in the model code when you order the unit. The model code is identified as follows: 651D X Y Z C D where: 651D Type Number...
Page 146
Appendix B: Model Code Explanation Interface (Y) The type of interface is indicated by a single digit code. Ordering Code RS-232 Valve Driver (Z) The valve driver is designated by a single letter code. Ordering Code Stepper motor Power Supply (C) Two power supplies are available, designated by a single number code.
Appendix C: Initial Settings Appendix C: Initial Settings Your 651 controller is shipped with the initial configuration settings listed alphabetically in Table 20. Since the 651 unit stores most of the settings in non-volatile RAM, the values are not default settings.
Page 148
Appendix C: Initial Settings Initial Settings (Continued) Parameter Initial Setting Other Sensor Signal Input Range 10 V Sensor Type Absolute None Set Point Control Pressure Position Soft Start Rate 100% User selectable; 0.1 to 100% Valve Failsafe Battery None Close, Open, Disable Back-Up Option Valve Signal Output Range Pressure: 10 V...
Page 149
Appendix C: Initial Settings This page intentionally left blank.
Appendix E: RS-232 Message Summary Appendix E: RS-232 Message Summary The RS-232 messages required for operation of the 651 controller are listed alphabetically—by command—in Table 20. For complete information on any RS-232 message, refer to Chapter Five: Remote RS-232 Operation, page 67. RS-232 Message Summary Command Description...
Page 153
Appendix E: RS-232 Message Summary 05 = Pa 05 = Pa 06 = cm H 06 = cm H 07 = in H 07 = in H H model / Firmware Version Reports the installed R 38 version • NO COMMAND version of firmware number G value...
Page 154
Appendix E: RS-232 Message Summary 2 = Close valve at 2 = Valve closes at power failure power failure Select High channel R7(w) Select Low channel Select Auto M x value M x value Gain R xx x: 1 = Gain SP A x: 1 = Gain SP A xx:46 = Gain SP A 2 = Gain SP B...
Page 155
Appendix E: RS-232 Message Summary 3 = Set Point C 2 = Set Point B 2 = Set Point B 4 = Set Point D 3 = Set Point C 3 = Set Point C 5 = Set Point E 4 = Set Point D 4 = Set Point D 6 = Analog Set Pt...
Page 156
Appendix E: RS-232 Message Summary 3 = Set Point C 27 = Set Point B 2 = Set Point B 4 = Set Point D 28 = Set Point C 3 = Set Point C 5 = Set Point E 29 = Set Point D 4 = Set Point D 6 = Analog Set Pt...
Page 157
Appendix E: RS-232 Message Summary RS-232 Message Summary (Continued) Command Description Request Response S 0 value Calibrate Analog Set Point Full Scale value: % of the analog set point FS voltage range Sensor Zero None None • corrects sensor zero offsets Z 2 value Special Zero...
Page 158
Appendix E: RS-232 Message Summary This page intentionally left blank.
Index Index A/D converter span calibration Cables local, 128 adapter, 13 Absolute pressure, calculating, 106 Calibration Analog set point analog set point, 64, 103 activating span of A/D converter, 128–30 local, 59 valve, 43, 73 RS-232, 99 Checksum status, 110, 127 calibration of Command priority and timing, 69 local, 64...
Need help?
Do you have a question about the 651D Series and is the answer not in the manual?
Questions and answers