Water Connection; Connecting Water; Water Quality - Swegon REACT Parasol Zenith 600 Installation, Commissioning Maintenance

Table of Contents

Advertisement

REACT Parasol Zenith c

Water connection

REACT Parasol Zenith 600 / 1200 / 1800
210
Dimensions, water connection length 600, 1200, 1800
B2
Värme retur/
Heating return
B1
Värme tillopp/
Heating supply
942256009
Water connection - Length 600, 1200 and 1800*
A1 = Inlet, cooling water ø12 x 1.0 mm (Cu)
A1 = Inlet, cooling water ø15 x 1.0 mm (Cu) *(Size 1800)
A2 = Return, cooling water ø12 x 1.0 mm (Cu)
A2 = Return, cooling water ø15 x 1.0 mm (Cu) *(Size 1800)
B1 = Inlet, heating water ø12 x 1.0 mm (Cu)
B2 = Return, heating water ø12 x 1.0 mm (Cu)

Connecting water

The water pipes are always placed on the product's short
side, regardless of the air connection side of the product.
Connect the water pipes using push-on couplings or
compression ring couplings when the product is ordered
without valves. Note that compression ring couplings
require support sleeves inside the pipes.
Do not use solder couplings to connect the water pipes.
High temperatures can damage the unit's existing soldered
joints.
Flexible connecting hoses for water are available for flat-end
pipes and valves, and can be ordered separately.
Connection dimensions
Model
Length
A cooling only
600, 1200
B Cooling/heating
600, 1200
A cooling only
1800
B Cooling/heating
1800
A cooling only
600, 1200
B Cooling/heating
600, 1200
A cooling only
1800
B Cooling/heating
1800
8
Swegon reserves the right to make design changes. 11/07/2022
210
A2
Kyla retur/
Cooling return
A1
Kyla tillopp/
Cooling supply
Factory-fitted
Connection Coupling type
Actuator and valve
Return
Actuator and valve
Return
Actuator and valve
Return
Actuator and valve
Return
-
Return
-
Return
-
Return
-
Return

Water quality

Swegon recommends water quality according
to VDI 2035-2 for both the heating and cooling
systems. In order to maintain the oxygen content
in the water below the levels (<0.1 mg/l) prescribed in VDI
2035-2, it is recommended to install a vacuum degasser,
particularly in the cooling system where it's more chal-
lenging to dissolved gas. It is also important that the pre-
pressure in the expansion vessel is dimensioned according
to EN-12828 for both the heating and cooling systems and
that regular checks are made of the pre-pressure. The cooling
and heating systems must be designed to prevent oxygen
from entering the system, this is particularly important to
consider when selecting flex hose, pipes and expansion
vessels. When the system is filled with fresh water, it has
an oxygen content of approximately 8 mg/l, however, this
oxygen is consumed quickly through corrosion processes
and within a few days the oxygen in the water should be
consumed. Nevertheless, it is important to avoid filling the
system with fresh water unnecessarily.
Automatic deaerators are often installed to facilitate filling
of the system. It is recommended that the automatic
deaerators are turned off once the system has been fully
vented to avoid these drawing in air in the system if the
pre-pressure in the expansion vessel should drop.
Note:
Use support sleeves inside the pipes
together with compression ring couplings.
Connection Coupling type
DN15, male thread
Supply pipe
DN15, male thread
Supply pipe
DN20 external threads
Supply pipe
DN20/DN15 external threads
Supply pipe
Plain pipe 12 x 1.0 mm
Supply pipe
Plain pipe 12 x 1.0 mm
Supply pipe
Plain pipe 15 x 1.0 mm
Supply pipe
Plain pipe 15/12 x 1.0 mm
Supply pipe
 
Plain pipe 12 x 1.0 mm
Plain pipe 12 x 1.0 mm
Plain pipe 15 x 1.0 mm
Plain pipe 15/12 x 1.0 mm
Plain pipe 12 x 1.0 mm
Plain pipe 12 x 1.0 mm
Plain pipe 15 x 1.0 mm
Plain pipe 15/12 x 1.0 mm