Siemens RUGGEDCOM RSG907R Installation Manual page 51

Hide thumbs Also See for RUGGEDCOM RSG907R:
Table of Contents

Advertisement

RUGGEDCOM RSG907R
Installation Guide
Test
IEC 61000-4-29
IEC 60255-27
EMC Immunity Type Tests per IEEE 1613
NOTE
The RUGGEDCOM RSG907R meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports. Class 1 allows for temporary communication loss, while Class 2 requires
error-free and interrupted communications.
Test
IEEE 1613
IEEE 1613
IEEE 1613
IEEE 1613
IEEE 1613
IEEE 1613
IEEE 1613.1
IEC 61000-4-10
EMC and Environmental Type Tests
Description
Voltage Dips and Interrupts
Dielectric Strength
HV Impulse
ESD
Radiated RFI
Fast Transient
Oscillatory
HV Impulse
Dielectric
Strength
Damped
Oscillating
Magnetic Field
100 kHz or 1 MHz
DC Power Ports
Signal Ports
2 kV (Failsafe Relay Output)
DC Power Ports
AC Power Ports
Signal Ports
5 kV (Failsafe Relay Output)
DC Power Ports
AC Power Ports
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Enclosure Ports
Test Levels
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
2 kV or 2.8kV DC
2 kV
5 kV
5 kV
Test Levels
± 8 kV
± 15 kV
35 V/m
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV
2.5 kV Common Mode @ 1 MHz
2.5 kV Common Mode @ 1 MHz
1 kV Differential Mode @ 1 MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kV (Failsafe Relay)
2.8 kVDC or 2 kV
2 kV
100 A/m for 1 s (100 kHz and 1 MHz)
Chapter 6
Certification
Severity Levels
41

Advertisement

Table of Contents
loading

Table of Contents