Outputs

The M2000 Rooftop controller contains 8 customizable outputs; five triac ON/OFF outputs (24VAC) and
three analog outputs (0-10VDC). Output configuration is performed via the ProLon Focus software.
An integrated resettable fuse protects each of the outputs of the M2000 against current surges and short
circuits. This protection will cut the current to the output as soon as an overload condition is detected.
The fuse is a round, yellow-coloured PTC that will change to orange and heat up on an overload condi-
tion. Once power has been removed from the M2000, the fuse will cool down and automatically reset. Fix
the faulty wiring and you will be able to activate the output once again.

Output Specifications

Output
Triac source 24VAC,
DO 1
Max Current: 300 mA
Triac source 24VAC,
DO 2
Max Current: 300 mA
Triac source 24VAC,
DO 3
Max Current: 300 mA
Triac source 24VAC,
DO 4
Max Current: 300 mA
Triac source 24VAC,
DO 5
Max Current: 300 mA
Configurable Analog Output:
- 0 to 10 VDC
AO 1
- 2 to 10 VDC
- 0 to 5 VDC
Max Current: 40 mA
Configurable Analog Output:
- 0 to 10 VDC
AO 2
- 2 to 10 VDC
Max Current: 40 mA
Configurable Analog Output:
- 0 to 10 VDC
AO 3
- 2 to 10 VDC
Max Current: 40 mA
REV. 6.1.8 / PL-HRDW-RTU-M2000-C/F-EN
Type
On-or-Off
On-or-Off
On-or-Off
On-or-Off
On-or-Off
Modulating Proportional /
Pulse /
On-or-Off
Modulating Proportional
Modulating Proportional
Action
Application
Fan
(G)
Cooling (1st Stage)
(Y1)
Cooling (2nd Stage)
(Y2)
Heating (W1) /
Preheat Permission
Heating (W2) /
Exhaust Fan
Exhaust or Ventilation) /
Baseboard
Preheating Only /
Preheat + Heating /
Heating
Economizer
Bypass /
Variable Speed Drive