User Guide
MMI-20019808
Note
Rockwell Automation PLCs have the first four bytes consumed by a device defined as
status information. This behavior is specific to devices from Rockwell Automation and is
not defined in the EtherNet/IP specification. However, since all known PLCs are
implemented this way, the Micro Motion EtherNet/IP Module adopts this behavior and
strips off the corresponding four bytes from the consumed data.
B.2.4
Port Object, Class F4h
Supported services
Class services:
Get Attribute Single
Get Attribute All
Instance services:
Get Attribute Single
Get Attribute All
Class attributes
#
Access
Name
1
Get
Revision
2
Get
Max Instance
3
Get
No. of instances
8
Get
Entry Port
9
Get
All Ports
Instance attributes, Instance 02h
#
Access
Name
1
Get
Port Type
2
Get
Port Number
3
Get
Port Object
Path Size
Path
4
Get
Port Name
User Guide
Type
Value
UINT
0001h
UINT
0002h
UINT
0001h
UINT
0002h
Array of STRUCT
0000h 0000h
{UINT; UINT;}
0000h 0000h
0004h 0002h
Type
Value
UINT
0000h
UINT
0002h
Struct of:
UINT
0002h
Padded EPATH
20 F5 24 01h
SHORT_STRING
"TCP/IP"
Device profile
January 2019
Description
Revision 1
2 is the highest instance number
1 instance is implemented
Returns the instance of the Port
object that describes the port.
Array of structure containing
attributes 1 and 2 from each
instance. Instance 1 is at byte offset
4. Instance 2 is at byte offset 8, etc.
The 4 bytes at offset 0 shall be 0.
(Default)
Comments
TCP/IP
Port 2
-
TCP class, Instance 1
Name of port
39

Advertisement

Table of Contents
loading