KEB COMBIVERT F4-S Series Instruction Manual page 16

Hide thumbs Also See for COMBIVERT F4-S Series:
Table of Contents

Advertisement

Operation of the Unit
Speed search
GB
Voltage stabilization
38
When connecting the frequency inverter onto a decelerating motor, an
error can be triggered by the differing rotating field frequencies. At
activated speed search the inverter searches the actual motor speed,
adapts its output frequency and accelerates with the adjusted ramp onto
the given set value. During speed search CP.2 displays "SSF". The
parameter determines, under what conditions the functions operate. With
several conditions the sum of the value must be entered.
Example: CP.16 = 5 means at control releas and after reset
Adjustment range:
Resolution:
Factory setting:
Customer adjustment: _______
This parameter can adjust a regulated output voltage in relation to the
rated frequency. Because of this voltage variations at the input as well as
in the intermediate circuit only have a small influence on the output voltage
(U/f-characteristic). The function allows, among other things, an adaption
of the output voltage onto the special motors. In the example below the
output voltage is stabilized onto 230 V (0% boost).
Adjustment range:150...649 V, oFF
Resolution:
Factory setting:
Customer adjustment: _______ V
U
/U
N
A
250 V
CP.17 = 230 V
190 V
0...7
Value Condtion
1
0
function off
0
1
at control release
2
at switch on
4
after reset
1 V
oFF
U
at U
= 250V unstabilized
A
N
U
at U
= 250V stabilized
A
N
U
at U
= 190V stabilized
A
N
U
at U
= 190V unstabilized
A
N
U
= mains voltage
N
U
= output voltage
A
CP.5 = 50 Hz
f

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents