5.11 Fuel treatment system – Initial start-up
Overview of fuel treatment system
1 Pressure-free overflow
2 Bypass 1
3 Bypass 2
4 Safety valve, 3 bar
5 Ball valve, inlet
6 Pressure gage
7 Ventilation, sample extrac-
tion
8 Differential pressure gage
Switching on fuel treatment system
1.
Switch on fuel treatment system (→ Page 106).
2.
Check differential pressure at differential pressure gage (8). Differential pressure in a new system: 0.1 bar to
0.3 bar.
Result:
If no differential pressure is measured, the coalescer filter element is probably being bypassed.
1. Remove coalescer filter element (→ Page 247).
2. Check sealing surfaces on coalescer filter element and in the pressure tank.
9 Ball valve, outlet
10 Check valve 700 mbar
11 Check valve 5 mbar
12 Return to overflow tank
13 Engine
14 Overflow tank
15 Filter water separator
16 Drain ball valve
MS15035/00E 2018-08 | Operation | 103
17 Automatic water drain
18 Water level electrode
19 Ball valve, sample extrac-
tion, inlet
20 Switchgear cabinet
21 Pump
22 Coarse filter
23 Fuel supply from tank
24 Tank

Hide quick links: