4-3-4
Programming
Assign the user-defined variables that is used in the user program on the CPU Unit to the memory used
for CJ-series Units that will be accessed by the E5C Controller by using AT specification.
Then, create the user program for communicating with the E5C Controller.
The user program gets the E5C Controller status from the upload area of the E5C Controller and
sends commands to the download area of the E5C Controller.
Refer to the NJ/NX-series CPU Unit Software User's Manual (Cat. No. W501) for memory used for
CJ-series Units and AT specification.
4-3-5
Connection Examples
An example of connecting three E5CC Controllers is given below.
NX1P2 CPU Unit
For an NX1W-CIF11
SW1
RDA- RDB+ SDA- SDB+ SHLD
Refer to the E5
on wiring an E5C Controller.
NX-series NX1P2 CPU Unit Built-in I/O and Option Board User's Manual (W579)
RS-422A/485 Option Board
NX1W-CIF11/CIF12
E5CC
Controller
No. 0
PV
SV
<< PF
E5CC
Operation setting DIP switches on the back of the
NX1W-CIF11/CIF12 Option Board
For an NX1W-CIF12
SW1
SW1
NX1W-CIF11/CIF12
E5CC
Controller
No. 0
B (+)
13
14
A (-)
C Digital Temperature Controllers Communications Manual (Cat. No. H175) for details
E5CC
E5CC
Controller
Controller
No. 1
No. 2
PV
PV
SV
SV
<< PF
<< PF
E5CC
E5CC
SW1
SW2
SW2
E5CC
E5CC
Controller
Controller
No. 1
No. 2
B (+)
B (+)
13
13
14
14
A (-)
A (-)
4 Serial Communications
Terminating
resistance
120 Ω (1/2W)
4
4 - 17