5 Installation Procedure
3.
Insert the option card (B) into the CN5-B (H) or CN5-C (I) connector on the drive
and fasten it into place using the included screws (C). Tighten both screws to 0.5 to
0.6 Nm (4.4 to 5.3 in. lbs).
Use the CN5-C connector (I) when connecting only one option to the drive; use both
CN5-B (H) and CN5-C when connecting two options.
Note: Installing the option card on a GA700, CR700, and CH700 drive requires only two screws and
does not require a ground wire. The option package ships with three screws and ground wires for
installation on other drive series. Do not use the ground wire or the extra screw.
Figure 15
I
H
4.
Prepare the wire ends as shown in
Figure 16
26
Figure 15 Insert the Option Card
Shield
PG option terminal
FE/SD
Figure 16 Prepare Ends of Shielded Cable
YASKAWA ELECTRIC TOBP C730600 75B YASKAWA AC Drive Option PG-B3 Installation Manual
B
C
Figure
16.
Insulation
PG at motor
Ground Terminal
Shield sheath
(Insulate with electrical tape
or heat-shrink tubing)