Table 5-20 lists all the I.D. codes and ranges or selections for the function
parameters in setup group "INPUT 2."
Table 5-20
Setup Group – Input 2
Parameter
Identifying
Description
Input 2 Type
170
Input 2 Transmitter
171
Characterization
Input 2 High Range
035
Value
Format
Code
Code
11
11
18
Continued
Range or Selection
1 to 24 = Unused
0 = Disable
25 = 0-20 mA
26 = 4-20 mA
29 = 0-5 Vdc
30 = 1-5 Vdc
31 = Unused
32 = Slidewire
Changing the Input Type will
result in the loss of Field
Calibration values and will
restore the Factory
Calibration values.
0 = B TC
1 = E TC H
2 = E TC L
3 = J TC H
4 = J TC L
5 = K TC H
6 = K TC L
7 = NNM TC H
8 = NNM TC L
9 = NM90 H
10 = NM90 L
11 = Nicrosil TC
12 = R TC
13 = S TC
14 = T TC H
15 = T TC L
16 = W TC H
17 = W TC L
18 = 100 PT RTD
19 = 100 PT LO RTD
20 = 200 PT RTD
21 = 500 PT RTD
22 = Radiamatic RH
23 = Radiamatic RI
24 = Linear
25 = Square Root
–999. to 9999. Engineering