3.1
Preparing the Controller for Communications,
Procedure
Table 3-2
Controller Procedure for Communication Parameters
Step
Press
1
Set Up
2
Function
16
RS422/485 ASCII Communications Option Product Manual
The procedure in Table 3-2 tells you what keys to press on the controller
keyboard, the upper and lower display indications, and the range of
settings available to you.
Use
to make adjustments to the range of setting or selection.
Lower Display
COM
Successive presses of the [FUNCTION] key will sequentially display all the
functions and their values or selections.
COMSTA
DIS
R422
MODB
ComADD
01 to 99*
*Address 00 disconnects it from
the link.
SDENAB
DIS
ENAB
SHDTIM
0 to 255
Sample periods
0 = No Shed will occur
PARITY
ODD
EVEN
BAUD
2400
4800
9600
19200
TX DLY
1 to 500 milliseconds
WS FLT
FP B
FPBB
FP L
FPLB
SDMODE
LAST
MAN
FSAF
AUTO
SHD.SP
LSP
CSP
Upper Display
Range of Setting
or Selection
Continued
Parameter Description
Communications
Communication State
Communication Address
Disable/Enable Shed
Function
Shed Time
Parity
Baud Rate (bits/second)
Transmission Delay
Timer
Word/Byte Order for
Floating Point
Communications Data
Controller Shed Mode
and Output Level
Shed Setpoint Recall