Table 5-4 Error Status Definitions - Honeywell UDC2300 Product Manual

Universal digital controller rs422/485 ascii communications option
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

5.4
Miscellaneous Read Only's - UDC2300,
Error status
definitions
Table 5-4
Error Status Definitions
Code
Error
001
Emergency Manual
002
Failsafe
004
Working Calibration
Checksum Error
008
Configuration Checksum
Error
016
Factory Calibration Error
032
Hardware Failure
064
Restart After Shed
128
Configuration /Calibration
Memory Changed
58
RS422/485 ASCII Communications Option Product Manual
Table 5-4 lists the UDC error status codes and their definitions.
Indicates that the output of the unit which has been in slave operations, is
under manual control, locally. Error remains until local control is relinquished
at the controller.
Error occurs whenever the control reverts to failsafe operation and remains
as long as the condition exists.
Indicates that an error exists in the working calibration data. Re-select the
inputs to load factory calibration data or field calibrate the inputs.
Error exists in the configuration data. Verify configuration data at the
keyboard. Checksum will be recomputed by stepping the controller through
the status tests.
Error exists in the factory calibration data and remains as long as the
condition exists.
Indicates either a RAM tests failure or Input 1, Input 2, Input 3 failure on two
consecutive conversions.
Error occurs whenever a shed of slave override is performed. Error is reset
following a WRITE command to I.D. code 255 (064).
Error occurs whenever shed, configuration, or calibration changed. Also
occurs whenever there is a change of state in 001, 002, 004, 008, or 016.
Error is reset following a Write command to I.D. code 255.
Continued
Definitions
10/00