DESIGN AND OPERATING PRINCIPLE
Warm stale extract air from the room flows into the unit, where it is filtered by the extract filter, then air flows through the heat exchanger and is
exhausted outside by the extract fan.
Clean cold air from outside is moved to the supply filter. Then filtered air flows through the heat exchanger and is moved to the room with the supply
fan. Heat energy of warm extract air is transferred to clean intake fresh air from outside and warms it up.
Heat recovery minimizes thermal energy losses and space heating expenses in cold seasons.
VUT/VUE 250 V mini A12/A1
Extract air
Supply air
Freeze protection
The heat exchanger freeze protection function of the unit is implemented with a temperature sensor or a thermostat depending on model. The
temperature sensor is installed in the exhaust air duct downstream of the heat exchanger. In case of a freezing danger (extract air temperature
downstream of the heat exchanger is +3 °C) the supply fan is turned off and the heat exchanger is warmed up with warm extract air flow. To set the
thermostat temperature set point set the temperature control knob into a respective position.
VUT/VUE 250 V mini A12/A1
VUT/VUE 250 H mini A12/A1
6
UNIT OPERATION LOGIC
Intake air
Exhaust air
Extract filter
Control unit
Supply fan
Drain pan
Drain pipe
Control unit
Extract filter
Supply fan
Drain pan
Drain pipe
Extract air
Supply air
UNIT DESIGN
VUT/VUE 250 V/H mini A12/A1
VUT/VUE 250 H mini A12/A1
Supply filter
Intake air filter with higher
level of filtering
Extract fan
Thermostat
Supply filter
Intake air filter with higher
level of filtering
Extract fan
Thermostat
www.ventilation-system.com
Intake air
Exhaust air