CONNECTION TO POWER MAINS

DISCONNECT THE UNIT FROM POWER MAINS PRIOR TO ANY OPERATIONS. THE UNIT MUST
BE CONNECTED TO POWER MAINS BY A QUALIFIED ELECTRICIAN. THE RATED ELECTRICAL
PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER'S LABEL.
DO NOT LAY THE CABLE IN CLOSE PROXIMITY TO THE CONTROL
PANEL CABLE! DO NOT COIL THE CABLE FROM THE CONTROL PANEL
IN LOOPS WHILE LAYING IT.
ANY INTERNAL CONNECTION MODIFICATIONS ARE NOT ALLOWED AND RESULT IN WARRANTY
LOSS.
Connect the unit to a single-phase AC 230 V/50 (60) Hz power mains by using the pre-wired power cord with the Euro Plug XP.
Connect the unit to power mains through the external automatic circuit breaker QF with a magnetic trip integrated into the fixed wiring system with
the rated current not below the rated current consumption (refer to the «Technical data» section).
XP
L
1
L
PE
2
PE
N
3
N
1
4
1
2
5
2
3
6
3
4
7
4
5
8
5
XP
L
1
L
PE
2
PE
N
3
N
1
4
1
2
5
2
3
6
3
4
7
4
5
8
5
www.ventilation-system.com
EXTERNAL CONNECTION DIAGRAM FOR THE A2 SPEED CONTROLLER
QF
230 V, 50/60 Hz
N M L
EXTERNAL CONNECTIONS DIAGRAM FOR THE A12 CONTROL PANEL
QF
230 V, 50/60 Hz
L
L
L1
L1
L2 L3
L2
IN
IN OUT OUT OUT OUT
OUT OUT OUT OUT
L
1
PE
2
N
3
1
4
2
5
3
6
4
7
5
8
L
1
L
PE
2
PE
N
3
N
1
4
1
2
5
2
3
6
3
4
7
4
L3
L4
L4
5
8
5
QF
XP
230 V, 50/60 Hz
L
PE
N
1
2
3
4
5
QF
XP
230 V, 50/60 Hz
N M L
2.5
E
E L3 L2 L1 L N
L3
L2
L1
L
N
13