Switching Off The Dib-R5 Advanced - Hytera ACCESSNET-T IP DIB-R5 advanced Operation Manual

Digital integrated base station
Hide thumbs Also See for ACCESSNET-T IP DIB-R5 advanced:
Table of Contents

Advertisement

Service interruption

Switching off the DIB-R5 advanced

Shutting down hardware components
➔ You have successfully shut down the hardware components.
5.2 Switching off the DIB-R5 advanced
The procedure for switching off the DIB-R5 advanced is described below.
Several on/off switches with redundant voltage supply feeds
With redundant voltage supply feeds (optional), the DIB-R5 advanced features two on/
off switches and two separate voltage sources, if necessary. Each of them has to be
switched off for the service interruption of the product.
Switching off the DIB-R5 advanced
Preparation:
n
The installed hardware components must have been shut down, refer to
Ä Chapter 5.1 "Shutting down hardware components" on page 77.
1.
2.
3.
➔ You have successfully switched off the DIB-R5 advanced.
78
Press the Power button on the hardware component to shut it down.
ð The software components are being shut down.
The indicators (LEDs) go out after approx. 5 to 20 seconds.
The hardware component is properly shut down if the "RUN" LED is off.
Set the on/off switch to the switch position "OFF", refer to Figure 8.
ð The integrated hardware components are switched off.
Switch off the voltage source at the location. Alternatively you can switch off the
fuse of the sub-distribution.
Risk of electric shock
Ensure by means of switch interlock that a source of electrical power cannot be
switched on unintentionally by an unauthorized third person.
Check whether all LED displays are inactive.
Operation Manual 90DIBR5advancedOM02 - 1.0