Configuration
BATTERY CONFIGURATION
Type
Float voltage
Recharge current
Autonomy time
Stop Operation time
Capacity
:
0033 Ah
ESC
Float voltage
Voltage to maintain battery charging.
Float voltage = Number of battery cells x battery float voltage per cell.
Typical battery float voltage per cell (ask the battery manufacturer for confirmation):
Lead-Acid (VRLA):
NiCd:
Boost:
Recharge current
Maximum battery recharge current.
Max 20% of battery capacity (Ah).
Example: 100Ah - max recharging current 20A.
Autonomy time
The autonomy time of the battery.
UPS autonomy on battery mode at full load condition.
This value is calculated based on the battery type, capacity and number of cells.
180 cells
Battery with expected trickle life 5 years
UPS model
10Ah
17Ah
SitePro 10 kVA
8*
15*
SitePro 15 kVA
-
10*
SitePro 20 kVA
-
6*
SitePro 30 kVA
-
SitePro 40 kVA
-
*) Autonomy time for battery supplied by GE UPS manufacturer.
186 cells
Battery with expected trickle life 5 years
UPS model
10Ah
17Ah
SitePro 10 kVA
8
15
SitePro 15 kVA
-
10
SitePro 20 kVA
-
6
SitePro 30 kVA
-
SitePro 40 kVA
-
Modifications reserved
OPM_SPE_XXX_10K_40K_8GB_V020.doc
BATTERY CONFIGURATION screen
Type
:
Lead Acid
Battery type (Lead Acid / NiCd / Boost).
:
409 V
:
003.3 A
Lead - Acid
:
006 min
NiCd
:
003 min
Cells
: 180
Boost
2.27 Vdc for cell
1.41 Vdc for cell
2.23 Vdc for cell
Autonomy times for lead acid batteries (VRLA)
Autonomy at full load at PF=0.8
24/26
33Ah
38Ah
Ah
28/30*
43*
50*
13/15*
24*
30*
9/10*
16*
20*
-
5/6*
10*
12*
-
6*
7*
Autonomy times for lead acid batteries (VRLA)
Autonomy at full load at PF=0.8
24/26
33Ah
38Ah
Ah
29/30
44
51
13/15
25
31
9/10
17
21
-
5/6
10
12
-
-
-6
7
Sealed Battery (VRLA).
Nickel Cadmium battery.
O
pen Batteries, which require sporadic refill
with distilled water.
180 cells x 2.27 Vdc = 409 Vdc
281 cells x 1.41 Vdc = 396 Vdc
180 cells x 2.23 Vdc = 401 Vdc
U floating = 409 Vdc (2.27 Vdc - cell)
Battery with expected trickle life 10 years
2x38
65Ah
75Ah 100Ah 150Ah 200Ah 300Ah 400Ah 500Ah
Ah
100*
120*
120
-
60*
70*
74
103
40*
50*
51
74
25*
30*
32
45
17*
20*
21
32
U floating = 423 Vdc (2.27 Vdc - cell)
Battery with expected trickle life 10 years
2x38
65Ah
75Ah 100Ah 150Ah 200Ah 300Ah 400Ah 500Ah
Ah
102
-
127
-
61
-
79
110
41
-
54
80
26
-
34
47
17
-
22
34
-
-
-
-
-
-
-
-
120
-
-
-
74
103
-
-
51
74
120
-
-
-
-
-
-
-
-
-
127
-
-
-
80
110
-
-
55
80
127
-
Continue
Operating Manual SitePro 10-15-20-30-40 kVA / S8
-
-
-
-
-
-
-
-
-
-
Page 74/99