LED Stop Operation (red colour)
It warns about the imminent inverter stop (default parameter = 3 min.) and the
consequent load shutdown as result of:
LED Alarm (yellow colour)
It blinks when one or more alarm is activated. The internal buzzer is ON.
The LED remains lighted (with the alarm condition still present) and the buzzer
stops when the key "MUTE" is pressed.
The LED Alarm is also lighted when the load is not protected by UPS or in case Q1 is
open.
LED Operation (green colour)
When lit, indicates that the UPS is functioning correctly and the load is system
protected (Load supplied either from inverter or from Automatic Bypass in case of
SEM functionality).
When blinking, indicates that a regular maintenance service is needed (SERVICE
REQUIRED).
May be reset by a service technician only.
See Section 11 – Maintenance – Service check.
The LED is OFF when the output switch Q1 is open, indicating that the Inverter is in
service mode, not supplying the load.
Modifications reserved
OPM_SPE_XXX_10K_40K_8GB_V020.doc
The battery is fully discharged and the load cannot be transferred on mains.
Overtemperature or overload condition (>125%) and the load cannot be
transferred on mains.
User LCD Interface
The user interface consists of a Back lit Graphic
Display (LCD) having:
Synoptic diagram indicating UPS status.
UPS
operating,
information.
History of events (alarms and messages).
Functionality can be programmed to meet
customer needs by changing parameters.
Operation commands of the UPS.
AC
and
DC
metering
Page 43/99