Home\Setup
SETUP
LEVEL 1
:
LEVEL 2
:
Home\Setup\User
DATE AND TIME
Date
:
Time
Home\Setup\User
MODEM
Enabled
Init
Alarm call
Delay
Tel 1
Tel 1 enabled
When editing this parameter the UPS considers that a blank character terminates the string.
If no blank character is found then all 40 characters are used.
Alarm call
This Y/N parameter controls the automatic events signalling through modem.
If this parameter is set to Y (Yes) the UPS itself will call the remote location when a new event occurs.
Delay
This parameter controls the delay between the occurrence of a new event and the modem dialing.
It is useful because since the events typically do not occur isolated but in certain sequences, you can eliminate
the need for multiple dial-outs for such a sequence of events.
Tel 1
This parameter specifies a first telephone number to be used for modem dial-out.
The telephone number has a maximum 40 characters and cannot contain blanks.
If the desired number is shorter than 40 characters, the string will finish with blanks.
Tel 1 enabled
This parameter Y/N specifies if the first telephone number (Tel 1) will be used for dial-out.
Modifications reserved
OPM_SPE_XXX_10K_40K_8GB_V020.doc
USER
SERVICE
D M
Y
01.06.2007
H M S
15:37:25
:
N
:
BEQV1X3&D0S0=2
:
N
:
30 sec
:
1
:
N
Setup screen
LEVEL 1
USER
Displays a sequence of screens with parameters which can
be user defined.
LEVEL 2
SERVICE
Service only allowed.
At this level the parameters access is protected by a code.
Date and time screen
Date
You can adjust the date of the real time clock
existing in the UPS by the means of this parameter.
The value you enter is thoroughly checked to be a
correct date in the format "DD.MM.YY".
Hour
You can adjust the time of the real time clock
existing in the UPS by means of this parameter.
The value you enter is thoroughly checked to be a
correct time in the format "HH.MM.SS".
The time is specified in 24-hour format.
Modem screen 1
Enabled
You can enable/disable with Y/N the remote control
through modem calls by using this parameter.
For modem connection, the default setting is for serial port
J3 on P4 – Customer Interface.
Init
This parameter presents the modem initialisation string.
It can be 40 characters long.
Page 56/99
Operating Manual SitePro 10-15-20-30-40 kVA / S8